Viessmann VITODENS 050-W Installation And Service Instructions Manual page 74

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Changing the gas type
Converting from LPG to natural gas
Converting the gas type at the control unit
1. Turn on the ON/OFF switch.
2. Press MODE and
for approx. 3 s.
"SERV" appears on the display
and "I" flashes.
3. Use / to select "5" and confirm
with OK.
"1" flashes on the display.
4. Use / to select "0" and confirm
with OK.
The burner has been switched to
operation with natural gas.
Checking the CO
See page 42.
74
simultaneously
content
2
(cont.)
5. Press MODE and
for approx. 3 s.
Service mode is terminated. Serv-
ice mode also terminates automati-
cally after 30 min.
6. Turn the ON/OFF switch off and on
again.
The selected gas type is now ena-
bled.
simultaneously