Viessmann VITODENS 050-W Installation And Service Instructions Manual page 57

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Fault display
(cont.)
Fault code
System character-
displayed
istics
51
No DHW heating
52
Burner blocked
59
No DHW heating
5A
Burner blocked
A9
Control mode with-
out influence from
OpenTherm device
b0
Burner blocked
b8
Burner blocked
E3
Burner in a fault
state
E5
Burner blocked
F0
Burner blocked
F1
Burner in a fault
state
F2
Burner in a fault
state
Cause
Short circuit, outlet
temperature sen-
sor
Short circuit, flow
sensor
Lead break, outlet
temperature sen-
sor
Lead break, flow
sensor
Communication
error, OpenTherm
device
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Fault in safety
chain
Internal fault
Internal fault
Max. flue gas tem-
perature exceeded
Temperature limit-
er has responded.
Troubleshooting
Measures
Check the sensor (see
page 66).
Check connections and
leads. Replace sensor if
necessary.
Check the sensor (see
page 66).
Check connections and
leads. Replace sensor if
required.
Check connections and
cable. Replace Open-
Therm device if necessa-
ry.
Check the sensor (see
page 67).
Check the sensor (see
page 67).
Check the temperature
limiter and connecting
leads (see page 65).
Check the ionisation
electrode and connecting
cables.
Replace control unit.
Check heating system fill
level. Check circulation
pump. Vent the system.
Check heating system fill
level. Check circulation
pump. Vent the system.
Check the temperature
limiter and connecting
leads (see page 65).
Press "Reset" (see
page 59).
57