Viessmann VITODENS 050-W Installation And Service Instructions Manual page 44

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
44
3. To check the CO
burner output can be adjusted man-
ually.
1. Press MODE.
2. / repeatedly until "SERV"
appears.
3. OK to confirm.
"OFF" appears on the display.
4. Use / to adjust the burner out-
put:
Shown on
display
_
20
_ _
40
_ _ _
60
_ _ _ _
80
_ _ _ _ _ 00
5. Confirm your setting with OK.
Note
This function terminates automati-
cally after 30 min; alternatively use
/ to set the burner output to
"OFF" after the test.
4. Set the upper heating output and
check the CO
The CO
content must be within the
2
following range for the respective
gas type. See table.
Gas type
E or H (G20)
P (G31)
(cont.)
content the
2
Burner out-
put
20 %
40 %
60 %
80 %
100 %
content.
2
CO
content
2
in %
7.5 – 10.5
10.0 – 12.0