Viessmann VITODENS 050-W Installation And Service Instructions Manual page 59

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Fault display
(cont.)
Fault code
System character-
displayed
istics
Fd
Burner blocked
FF
Burner blocked
–––
Burner blocked
Reset (reset burner control unit)
Press À and ¿ simultaneously.
––– is displayed.
If the fault has been removed, "¨"
extinguishes and the default display is
shown or further faults are displayed.
Cause
Burner control unit
fault
Burner control unit
fault
Communication
error between
burner control unit
and programming
unit
Checking the programming unit soft-
ware version
Press À and
Troubleshooting
Measures
Check ignition electrodes
and connecting cables.
Check whether a strong
interference (EMC) field
exists near the appliance.
Press "Reset" (see
page 59).
Replace control unit if
fault persists.
Check ignition electrodes
and connecting cables.
Check whether a strong
interference (EMC) field
exists near the appliance.
Press "Reset" (see
page 59).
Replace control unit if
fault persists.
Check the connecting
lead.
Press "Reset" (see
page 59).
Replace burner control
unit or programming unit
if the fault persists.
simultaneously.
59

Advertisement

Table of Contents
loading

Table of Contents