2.6 Terminator Resistor Setup

In order to minimize the reflection effects on the CAN bus line, the CAN
bus line has to be terminated at both ends by two terminator resistors as in the
following figure. According to the ISO 11898-2 spec, each terminator resistor is
120Ω (or between 108Ω~132Ω). The bus topology and the positions of these
terminator resistors are shown as following figure.
Device 1
Each I-2533 includes one build-in 120Ω termintor resistor, users can
decide if it is enabled or not. The DIP switch for terminator resistor is under the
power connector.
Figure 2-6 Location of Terminator Resistor DIP Switch
The following DIP switch statuses present the condition if the terminator
resistor is active (default) or inactive.
Device 2
Figure 2.5
CAN bus network topology
C
terminator resistor
I-2533 User Manual (ver. 1.1, 2013/05/31) ------12
. . .
CAN_H
CAN_L
DIP switch for
Device N