No.
Part to be replaced
Fan motor, fan, fan case
(continued)
Drain pan
Work procedure
5) Attach the fan case (lower) in the same way as before
replacement. After confirming that the fan turns
smoothly without touching the fan case, screw the fan
case to secure.
6) Install the reinforcing plate in the same position as
before replacement.
7)
Re-connect the motor wiring in the same way as
before replacement, and attach the electric parts
box cover. Be sure to re-connect the wiring within
the electrical parts box in the same way as before
replacement.
8)
Attach the panel under the air intake to the same
position as before replacement.
1. Detachment
1) Remove the panel under the air intake.
(See the 1. of ①)
2) Remove the screws to secure the bottom plate.
(4 pcs (screws locate under the cross slit on the
heat-insulating material))
3) Slide the bottom plate in arrow direction as right figure,
and open the bottom plate using the hinge part as a
shaft.
4) Hold handles on the drain pan, and pull off slowly.
Do not hold the drain sockets when
removing the drain pan. (It may cause water
leakage.)
2. Attachment
1) Hook the edge (thin side) of the drain pan first, and
then push in the other side.
2) Screw to attach the bottom plate.
- 212 -
Remarks
Motor leads
Refrigerant
piping side
Fan case (upper)
Screws (3 points)
Hinge part
Screws (4 pcs)
Do not handle drain
sockets.
Drain socket
Drain pan
Push in the edge of
the drain pan
Bottom plate
Handle