Toshiba MMU-UP0091HP-E Service Manual page 123

Air conditioner (multi type)
Hide thumbs Also See for MMU-UP0091HP-E:
Table of Contents

Advertisement

Indoor service monitor list
Code No.
00
Room temperature (Use to control)
01
Room temperature (Remote controller)
02
Indoor suction air temperature (TA)
03
Indoor coil temperature (TCJ)
04
Indoor coil temperature (TC2)
05
Indoor coil temperature (TC1)
06
Indoor discharge air temperature (TF) **
07
Indoor fan motor number of revolutions**
08
Indoor PMV opening
F3
Filter sign time
Suction temperature of air to air heat
F9
exchanger (TSA) **
Outside air temperature (TOA) **
FA
* When the units are connected to a group, data of the header indoor unit only can be displayed.
** There is also a model which cannot be displayed.
• Refer to the service manual of an outdoor unit for "outdoor service monitor list".
Data name
Display format
- 123 -
Unit
Remote controller display example
×1
°C
×1
°C
×1
°C
×1
°C
×1
°C
×1
°C
×1
°C
×1
[0600] = 600rpm
rpm
×1/10
pls
[0150]=1500pls
×1
h
[2500] = 2500h
×1
[0024] = 24°C
×1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmu-up0121hp-eMmu-up0151hp-eMmu-up0181hp-eMmu-up0241hp-eMmu-up0271hp-eMmu-up0301hp-e ... Show all

Table of Contents