Table 1. Setting data (CODE No. table (example))
CODE No. (DN)
01
Filter sign lighting time
02
Filter pollution level
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
19
Louver type (wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2b
Thermostat output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
5d
High ceiling SW
60
Timer setting (wired remote controller)
77
Dual set point
b3
Soft cooling
b5
Occupancy sensor: Provided/None
Occupancy sensor: Enable/Invalid
b6
(Judgment time of absence)
b7
Occupancy sensor: Operation at absent time
d0
Remote controller operation save function
F0
Swing mode
F1
Louver fixing position (Flap No. 1)
F2
Louver fixing position (Flap No. 2)
F3
Louver fixing position (Flap No. 3)
F4
Louver fixing position (Flap No. 4)
F6
Presence of Application control kit
Fd
Priority operation mode (FS unit)
FE
FS unit address
Table 2. Type: Code No.10
Setting data
4-way cassette
0001
Concealed Duct Standard
0004
Concealed Duct High static pressure
0006
Ceiling
0007
High Wall
0008
Concealed Duct High static pressure
0016
fresh air intake
Console
0018
Item
)
Type
Model name
MMU-UP****HP
MMD-UP****BHP
MMD-UP****HP
MMC-UP****HP
MMK-UP****HP
MMD-UP****HFP
MML-UP****NHP
- 167 -
Setting data
Depending on Type
0000: standard
0099: Not determined
Depending on Type
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts ±1.5)
0000: None
0000: Thermostat ON
0000: Not available
0000: Body sensor
0000: Standard
0000: Available
0000: Unavailable
0001: Available
0000: None
0002: Enable (60 min.)
0000: Stand by
0001: Enable
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: None
0000: Heating
0099: Unfixed
Table 3. Indoor unit capacity: Code No.11
Setting data
0000*
0044
0041
0001
0003
0005
0007
0009
0011
Factory-set value
Model
Setting data
Invalid
0012
0013
003 type
0015
005 type
0017
007 type
0018
009 type
0021
012 type
0023
015 type
0024
018 type
024 type
0025
Model
027 type
030 type
036 type
048 type
056 type
072 type
096 type
112 type
128 type