Handling-Diagram / Short Reference - janitza Prophi 12R Manual

Power factor controller
Table of Contents

Advertisement

Prophi
12R / 12 RS
®
By pressing the cursor buttons (up / down)
the stage display mode can be changed
AUTO MODE
---------------
j
cos
1.000 IND
1 2 3 4 5 6 7 8 9 10 11 12
1
LINE VOLTAGE
230.0 V-L/N
2
CURRENT [1]
200.0 A
3 REACTIVE POWER
88.88 kvar
4
ACTIVE POWER
88.88 kW
5 APPARENT POWER
88.88 kVA
6 DIFF. REACT POWER
88.88 kvar
7
FREQUENCY
50.0 Hz
8
TEMPERATURE [1]
25 °C
9
HARMONICS [ 3. ]
V: 0.5% - I: 0.1%
10 HARMONICS THD rel.
V: 0.5% I: 0.3%
11 SYSTEM-POWER
88.88 kvar
12
ENERGY [1]
88.88 kWh ( + )
13
DATE - TIME [1]
06.11.2015
- 10:13:40
14
SOFTWARE
VERSION ....
BACK TO 1
After 60 sec. without pressing
any button, automatic change
to auto-mode
Settings shown with grey background
colour are active only in case
of certain other settings.
If not needed they are not displayed.
32
PROGRAMMING
0
LANGUAGE
[ ENGLISH ]
1
I-CT PRIMARY
[ 1000 ] A / X A
2
I-CT SECONDARY
1000 A / [5] A
3
END STOPP [12]
4
CONTROL SERIES [1]
[1 1 1 1 1 1 1 1 1 1 1 1]
5
CONTROL MODE [2]
[ INTELLIGENT ]
6
POWER 1. STAGE
[ 25 ]. 00 kvar
7
TARGET
cos Phi [ 0.98 IND ]
8
MEAS. VOLTAGE
[ 230 ] V - L/N
9
V - CT RATIO
[ NO ]
10
SWITCH-IN TIME
[ 40 ] sec.
11 SWITCH-OFF TIME
[ 40 ] sec.
12
DISCHARGE TIME
[ 60 ] sec.
13
ALARM TEMP.
[ 55 °C ]
14
ALARM RELAY [3]
[ ERROR inverse]
15
FAN TEMP.
[ 30 °C ]
- 31 -
16
HARMONICS
THD-V [ 7 ] %
16
HARMONICS
THD-I [ -,- ] %
17
HARMONICS
[ 3. 5. 7. - 19.]
18
CONTRAST
* * * * * [ 4 ] * * * * *
2
19
I-CT PRIMARY
[ 1000 ] A / X
2
20
I-CT SECONDARY
1000 A / [5] A
2
21
END STOPP [12]
2
22 CONTROL SERIES [1]
[1 1 1 1 1 1 1 1 1 1 1 1]
23 CONTROL MODE [2]
2
[ INTELLIGENT ]
2
24
POWER 1.STAGE
[ 25 ]. 00 kvar
2
25
TARGET
cos Phi [ 0.98 IND ]
2
26 SWITCH-IN TIME
[ 40 ] sec.
2
27 SWITCH-OFF TIME
[ 40 ] sec.
2
28 DISCHARGE TIME
[ 60 ] sec.
29
Q - OFFSET
[ NO ]
BASIC SETTINGS
RESET - NO -
BACK
AUTO-INIT*
[ NO ]
1 CURRENT TRANSF.
[ KNOWN ]
2
I-CT PRIMARY
[ 1000 ] A / X
3
I-CT SECONDARY
1000 / [5] A
4
POWER 1. STAGE
[ 25 ].00 kvar
TEST 1...3
(automatic TEST RUN)
* AUTO INIT exists only,
if in „ExpertMode 2":
„2 Auto-Init Error = YES"
Changing
of values
by buttons:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prophi 12rs

Table of Contents