janitza Prophi 12R Manual page 28

Power factor controller
Table of Contents

Advertisement

Prophi
12R / 12 RS
®
Application:
Coupling of two PFC-systems using 2 PF-controllers
The coupling of two compensation systems via the interface of PF-controllers Prophi12RS offers
following advantages:
- no sum current transformer and no current transformer switching required
- easy installation, real dynamic compensation of both compensation systems
Feed 1
Transformer 1
Ct1
X / 5A
Consumer (1)
Prophi 12RS
(Master)
Capacitor system 1
Application example:
Two separate systems operate at two transformers; a coupling via a coupling switch exists between
both systems
1) Coupling is open: Both systems work completely independent.
2) Coupling is closed: Due to controller coupling, the two PFC systems are operated in PARALLEL
(symmetrically) or in SERIES (as extension).
Undesired interactions of the compensation system are avoided during operation at a common
bus bar (oscillation).
Description:
During controller coupling each controller measures its respective current. The measuring values of
reactive power difference are transmitted via interface to the „Master". The "Master" controls and
synchronizes the switching of both controllers. No additional installation required.
Installation:
The coupling of the 2 PF-controllers Prophi 12RS is done via interface (RJ45 plug) using a standard
LAN-cable CAT5 . The 110...230~ signal "Coupling switch closed" has to be conducted to the potential
free external input of a controller ( "Master").
Programming:
1. "Master": Menu INTERFACE /
3 EXTERNAL INPUT:
11 BAUDRATE:
2. Controller of 2nd system: Menu INTERFACE/
10 PROTOCOL COM1:
11 BAUDRATE COM1:
12 ADRESS:
No additional settings are required.
NOTE: In coupling mode C-TEST is inactive!
28
Coupler
ext. input (110...230V~)
LAN-cable (CAT5/CAT6)
Interface
(RJ45)
Prophi 12RS
(Slave)
COUPLING PAR. (systems will switching symmetrically) OR
COUPLING SER. (systems will switching one after another)
free (but the same at each device)
MODBUS RTU
equal to Master-controller
1
Feed 2
Transformer 2
Ct2
X / 5A
Consumer (2)
Interface
(RJ45)
Capacitor system 2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prophi 12rs

Table of Contents