Commissioning

6.6 Device Address

6.6
Device Address
Note
The address can only be changed from a remote master such as NI-FBUS Configurator or
DeltaV. For further details see Addressing in the manual,
instruments (7ML19985MP01)
Read only. The unique address of the device on the network.
1. In PROGRAM mode, navigate to: Level Meter > COMMUNICATION (5.) (Page 156) >
Device Address (5.2.) (Page 156) to view the device address.
2. Press Mode to return to Measurement mode.
6.7

Application example

The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to
empty.
Fill rate
Therefore SLOW response rate (0.1 m/minute) can be selected.
58
= 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time]
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
sensor reference point
high calibration point
1.0 m
15.5 m
level
low calibration point
.
Operating Instructions, 06/2018, A5E34648692-AE
Foundation Fieldbus for Level
LR560 (FOUNDATION FIELDBUS)