The user must analyze all aspects of the application, follow applicable industry standards, and follow the information concerning the product in the current product catalog and in any other materials provided from Parker or its subsidiaries or authorized distributors.
Operation Manual Series TDP/TEP 1. Introduction ® Parker 2-way servo proportional valves with VCD technology have an integrated electronics and re- quire only one sole electrical common for the control system. Different flow sizes are available to achieve an optimal adaption for different applications.
Code Seal Please order connector separately. for HFC fluid Angle female connector must be used for NG25 to NG50. For HFC fluids suitable Please order female connector M12 x 1 separately (order no.: 5004109). TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
If valves with onboard electronics are used in safety-related parts of control systems, in case the safety function is requested, the valve electronics voltage supply is to be switched off by a suitable switching element with sufficient reliability. TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
6 + PE acc. EN 175201-804 Wiring min. [mm²] 7 x 1.0 (AWG16) overall braid shield Wiring lenght max. [m] 50 Block Diagram of Integrated Electronics Do not connect with the supply voltage zero. TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Service Do not disassemble the valve! In case of Workings in the area of installation, commissioning, suspicion for a defect please contact Parker. maintenance and repair of the valve may only be Storage allowed by qualified personnel. This means persons...
HFC: choose the right seal option for series TEP. Special gaskets may be available depending on Choose seal option code N for series TDP. the utilized fluid. In case of doubt please consult Parker. TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
8...12 mm Cable length max. 50 m Female connector (ordering no. 5004072) For NG63 up to NG100 For cable lengths > 50 m consult Parker. 7/8-20 max. 67 UNEF-2B The connection cable is coupled to the female connector by solder joints.
(cross section AWG 6). Wiring Diagram of Supply Voltage control system valve 22...30 V 4 Am TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Page 12
4…12 mA 0…-10 V 4…12 mA 0…+10 V 12…20 mA 0…+10 V 12…20 mA 0…-10 V Cable break, Cable break, 0…3.6 mA 0…3.6 mA 12.5 V 12.5 V Overload 12.5 V Overload 12.5 V TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
The PC software can be downloaded free of charge Plug for at www.parker.com/isde - see page “Support” or parametering interface directly at www.parker.com/propxd. For program installation and software operating please see operation manual 5715-687.
Page 14
Closer information can be can be displayed via the ProPxD Parametrier software. Error code Error code Error description (additive) no errors over current cable break command signal cable break feedback signal undervoltage error bus communication error hardware failure TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
2006/42/EC. Length Max. 50 m Electronic Control System For lengths >50 m please contact Parker. The D3DW valve must be operated by the user The sealing surface of the valve must be with a suitable control system. properly connected to the earthed frame of The valve is connected using separate wires for the machine.
Page 16
Leaking only way to ensure that position control works plugs may constitute a safety hazard, so the properly valve must be returned to the manufacturer TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Page 17
To guarantee that the main piston operates reliably at all times, the minimum pilot pressure must be provided. To achieve this, a suitable combination of flow and return arrangements must be selected for the pilot oil. TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Page 18
Operation Manual Series TDP/TEP Declaration of Conformity unacceptable degree. This would invalidate Any unauthorised structural change or addi- the declaration of conformity supplied with tion to the product may jeopardise safety to an the product. TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Page 19
• Voltage spikes occurring when inductive loads • Connections must follow the connection list. are removed should be eliminated using a suitable protection circuit, for example flyback diodes. Connection Diagram Only guaranted with screened cable and female connector TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
Page 20
When the trip point is reached, pin 4 is non conducting, this means a normally closed function. Simultaneously pin 2 becomes conduct- ing, this means a normally open function. Wirings Installation Please order plug M12x1 separately. Order no.: 5004109 TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...
X X contacts of central connector contaminated clean contacts / replace plug feed cable interrupted fix feed cable X X X X X X wiring sequence incorrect correct wiring sequence X feed cable without shielding change cable grade TDP_TEP 5715-697UK.indd 05.11.20 Parker Hannifin Corporation...