Program Setpoints Menu - Eaton Cutler-Hammer MP1 Series Instructions Manual

Automatic transfer switches 30-1200a
Table of Contents

Advertisement

I.L.15.01.T.K.

9. Program Setpoints Menu

This table is a guide to the program setpoints menu. An explanation is given for each prompt that
will appear as the Menu Select key is pressed.
Program
Setpoint Display
Lang:
Current Day:
Current Hour:
Current Min:
Nom.Volt:
Nom .Freq:
Phases:
TDNE:
TDES:
TDEN:
TDEC:
TDN:
TDN:
TPRE:
N-UV-DO:
N-UV-PU:
E-UV-DO:
E-UV-PU:
N-OV-DO:
N-OV-PU:
E-OV-DO:
E-OV-PU:
N-UF-DO:
N-UF-PU:
E-UF-DO:
E-UF-PU:
N-OF-DO:
N-OF-PU:
E-OF-DO:
E-OF-PU:
Pref.Src:
P.S. Select
Man. Retransf.
Test/Area Prot
Plant Exerciser:
PE Load Transf:
Engine Run:
Test Day:
Test Hour:
Test Min:
Note: Highlighted options are exclusive to the MP1-E Controller
Effective June 2000
Setpoint
Possibilities
English, French
Mon-Sun
0-23
0-60
110 VAC – 240 VAC
110VAC – 600VAC
50Hz or 60Hz.
1 or 3
0 sec. to 1800 sec.
0 sec. to 120 sec.
0 sec. to 1800 sec.
0 sec. to 1800 sec.
-none-, N to E, E to N,
global
0 to 120 sec.
0 to 255 sec
50% to 99% of nominal
(dropout +2%) to 99%
50% to 99%
(dropout +2%) to 99%
105% to 120%
(dropout -2%) to 120%
105% to 120%
(dropout -2%) to 120%
90% to 99% of nominal
(dropout +1Hz) – 99%
90% to 99% of nominal
(dropout +1Hz) – 99%
103% to 110%
(dropout –1Hz) – 110%
103% to 110%
(dropout –1Hz) – 110%
enable or disable
S1, S2 or none
Y or N
Y or N
Y or N
Y or N
0 – 600min.
--- ,or Mon-Sun
0-23
0-60
Display
Explanation
Language the controller displays messages
Current Day – requires to only be set once
Current Hour
Current Min
System operating voltage
System operating frequency
Single phase or Three Phase system
Time Delay Normal to Emergency
Time Delay Engine Start
Time Delay Emergency to Normal
Time Delay Engine Cooldown
Time Delay in Neutral position. Can be
selected when transferring in one direction only
or both
Time Delay Neutral
Pre-Transfer Time Delay
Source 1 Undervoltage Dropout (% of nominal)
Source 1 Undervoltage Pickup (% of nominal)
Source 2 Undervoltage Dropout (% of nominal)
Source 2 Undervoltage Pickup (% of nominal)
Source 1 Overvoltage Dropout (% of nominal)
Source 1 Overvoltage Pickup (% of nominal)
Source 2 Overvoltage Dropout (% of nominal)
Source 2 Overvoltage Pickup (% of nominal)
Source 1 Underfrequency Dropout (Hz)
Source 1 Underfrequency Pickup (Hz)
Source 2 Underfrequency Dropout (Hz)
Source 2 Underfrequency Pickup (Hz)
Source 1 Overfrequency Dropout (Hz)
Source 1 Overfrequency Pickup (Hz)
Source 2 Overfrequency Dropout (Hz)
Source 2 Overfrequency Pickup (Hz)
Preferred source enable or disable
Preferred source select. Source 1(Normal),
Source 2(Emergency) or None (source
currently connected)
Pushbutton input for manual return to normal
Test/Area protection enable or disable
Plant Exerciser enabled or disabled
Plant Exerciser Engine test with or without load
Engine run time on exercise
Plant Exerciser Day of the week
Plant Exerciser Hour
Plant Exerciser Test Minute
Page 15