5. Performance Specifications

The performance specifications for the ATS-MP1 Controller Board are given in Table 2:
Table 2 – Performance Specifications
Input Control Voltage
Voltage Measurements of:
Voltage Measurement Range:
Voltage Measurement Accuracy:
Frequency Measurements of:
Frequency Measurement Range:
Frequency Measurement Accuracy
Undervoltage Dropout Range:
Undervoltage Pickup Range:
Overvoltage Dropout Range:
Overvoltage Pickup Range:
Underfrequency Dropout Range:
Underfrequency Pickup Range:
Overfrequency Dropout Range:
Overfrequency Pickup Range:
Operating Temperature Range
Storage Temperature Range
Operating Humidity
Generator Start Relay
Alarm Relay
Table 3 - Applicable Test Standards
UL 991
Canadian Standards Association Conformance (CSA)
UL 1008 / CSA 22.2 No 178.22
Dielectric test
FCC Part 15
Conducted/Radiated Emissions (Class A)
CISPR 11
Conducted/Radiated Emissions (Class A)
IEC 1000-2
Electrostatic Discharge test
IEC 1000-3
Radiated Susceptibility tests
IEC 1000-4
Fast Transient tests
IEC 1000-5
Surge Withstand tests
Effective June 2000
(50-150)% of V
(IN,RMS)
Normal Source V
AB
Normal Source V
BC
Normal Source V
CA
0 to 360 VAC RMS (50/60Hz) – MP1
0 to 750 VAC RMS (50/60Hz) – MP1-E
± 2% of reading over the monitoring range
Normal Source (S1), Emergency Source (S2)
40 Hz to 70 Hz
± 0.3 Hz over the measurement range
50% to 97% of the nominal system voltage
(Dropout +2%) to 99% of the nominal system voltage
105% to 120% of the nominal system voltage
103% to (Dropout –2%) of the nominal system voltage
90% to 97% of the nominal system frequency
(Dropout + 1Hz) to 99% of the nominal system frequency
103% to 110% of the nominal system frequency
101% to (Dropout – 1Hz) of the nominal system frequency
-20°C to + 70°C
-35°C to + 85°C
0 to 95% relative humidity (non-condensing)
5A, 1/6 HP @ 250VAC
5A @ 30VDC with a 30W maximum load
10A, 1-3 HP @ 250VAC
10A @ 30VDC
50/60 Hz
Emergency Source V
AB
Emergency Source V
BC
Emergency Source V
CA