SLC, transducer-controlled option
From main power panel
XXX VAC, 3-phase, 60 Hz
Main disconnect switch provided by others
Ground wire
L1
L1
L2
L2
L3
L3
Fuses 2A
Control panel - transformer
XXXV - 120 V, 100 VA
Controls
115 VAC
Pressure transducer
High-level alarm float
switch
Low-level alarm float
switch
Push-to-Silence alarm
Pump failure
Fig. 6
Wiring diagram, SLC with submersible analog level pressure transducer
L1
T1
L2
T2
L3
T3
CB xxA
K11
F1
F2
H1
H*
X1
X2
CB 10A
+
24 V
power supply
L1
N
+
-
LOGO
L+
M
500
Ohm
+
-
24V
Trans
-
i8
i2
3
2
3
1
i1
NIBP
i5
K02
21
22
i6
K03
21
22
Hand
Q1
Q3
Q4
Pump over-
temperature sensor
OLR
96
5
4
Seal sensor
6
K01
12
11
7
Alarm contact
1
Pump
OLR
xxA
XXX VAC, 3-phase, XX hp
PLC
text display
To LOGO
24 VDC
-
power supply
From
display
screen
PLC
Auto
K02
K03
OFF
11
14
11
14
Motor contactor
K11
A1
A2
Pump run light
X2
X1
G
Beacon alarm light
R
Alarm relay
K01
A1
A2
Audible alarm
A
+
-
Pump overload relay or
95
K02
overtemperature sensor
A1
A2
Pump seal-failure sensor
K03
A1
A2
11
14
8
9
Factory wire
Field wire
9