9.9.3 Block names, DLC, float-switch-controlled option
The following block names are used.
All adjustable parameters DO NOT use the same type of blocks. Check the block types below to determine which steps apply to your
application.
Block names
Description
HLA Dly
High-level alarm delay
MinRunT
Minimum pump run time
Pmp1Lead
Pump 1 as lead (duty) pump
Pmp2Lead
Pump 2 as lead (duty) pump
Example, changing adjustable parameter blocks, DLC, float-controlled option
Step
Action
• Press the "
" button repeatedly until the display does not change.
• To begin the configuration process, press the "ESC" button.
1
• Press the "
" button to select "Set Param".
• Then press the "OK" button.
Warning
2
Do not select "Stop". Doing so may erase the panel programming, which cannot be
restored without the use of an EEPROM card, which is not included with the panel.
If "Stop" is selected accidentally, a confirmation screen will appear. Select "No" and
press the "OK" button immediately.
36
Factory default setting
Time range
5 seconds
MM:SS
1 second
MM:SS
Off
On/Off
Off
On/Off
Block type
Timed/Demand
Timer
Both
Timer
Demand
Soft button
Both
Soft button
Both
Illustration