9.3 DLC, float-switch-controlled option

The alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.
Alarm screen Alarm text
1
High Level Alarm
2
Pump 1 Fail Alarm
3
Pump 2 Fail Alarm
Data screen System data
4
Pump 1 CT & ETM
5
Pump 2 CT & ETM
6
High Lvl CT
Pump 1 & 2 Lag Event
7
Counters
8
Power Fault Counters
9
Pump 1 & 2 Fault Counters

9.4 DLC, transducer-controlled option

The alarm screen will only be displayed when alarms are active. The alarm screen shows the date and time when the alarm started.
Alarm screen Alarm text
1
Xducer Sig
2
High Level Alarm
3
Low Level Alarm
4
Pump 1 Fail Alarm
5
Pump 2 Fail Alarm
Data screen System data
6
Current Tank Level
7
Pump 1 CT & ETM
8
Pump 2 CT & ETM
9
High Lvl CT & Low Level CT
10
Power Faults & Operating Hr
11
Transducer Signal
12
On/Off Level Settings
13
Lag Level Setting
14
High/Low Level Settings
15
Transducer Input
16
Minimum Run Time
17
High Level Pump Run Time
18
High Level Alarm Delay
22
Description
High level alarm
Pump 1 failure alarm
Pump 2 failure alarm
Description
Pump 1 cycles are shown at the top of the screen and pump 1 run time beneath.
Pump 2 cycles are shown at the top of the screen and pump 2 run time beneath.
High level alarm events
Pump 1 lag (standby) events are shown at the top of the screen and pump 2 lag
(standby) events beneath.
Power failures are shown at the top of the screen and hours in service beneath.
Pump 1 failure events are shown at the top of the screen and pump 2 failure events
beneath.
Description
Is activated when the transducer signal is below 3 mA.
When lifted, this float switch activates the alarm indication on the screen and the audible
alarm.
When lowered, this float switch stops the pump and activates the indication on the
screen.
Is activated when pump 1 overtemperature sensor, seal failure sensor or overload relay
has tripped.
Is activated when pump 2 overtemperature sensor, seal failure sensor or overload relay
has tripped.
Description
Liquid level in tank or pit in feet
Pump 1 cycle counter is shown at the top of the screen and pump 1 run time in minutes
beneath.
Pump 2 cycle counter is shown at the top of the screen and pump 2 run time in minutes
beneath.
High level alarm counter is shown at the top of the screen and low level alarm counter
beneath.
Power failure counter is shown at the top of the screen and operating hours beneath.
Raw value of transducer reading, in mADC
Pump on and off level setpoints
Lag (standby) pump on level setpoint
High- and low-level alarm setpoints
Transducer range and offset settings
Minimum pump run time per cycle
Minimum high level pump run time per cycle
Elapsed time between high level point and alarm activation