Grundfos SLC Series Installation And Operating Instructions Manual page 40

Simplex and duplex pump control panels
Table of Contents

Advertisement

Example, changing adjustable parameter soft-button blocks, DLC, transducer-controlled option
See the below example of the lead (duty) and lag (standby) pump settings and how to navigate through the screens.
Step
Action
• Press the "
" button repeatedly until the display does not change.
• To begin the configuration process, press the "ESC" button.
1
• Press the "
" button to select "Set Param".
• Then press the "OK" button.
Warning
2
Do not select "Stop". Doing so may erase the panel programming, which cannot be
restored without the use of an EEPROM card, which is not included with the panel.
If "Stop" is selected accidentally, a confirmation screen will appear. Select "No" and
press the "OK" button immediately.
• Press the " " or "
• In this example, "P1&3Lead" is being viewed.
3
• The bottom line indicates the current state of the soft-button switch.
• In this example, the soft-button is set to "On".
• To change the set value for the parameter, press the "OK".
4
• The cursor will appear on the switch parameter.
• To change the value of the soft-button switch, press the " " or "
• In this example, the set value has been changed from "On" to "Off".
5
• When the desired time value has been entered, press the "OK" button.
• The new value will now be in effect.
6
• Press the "ESC" button twice to exit parameter mode.
7
40
" button to view the parameter values.
Illustration
" button.