Crane Barnes SE51 Series Installation Manual

Submersible sewage ejectors .4hp, 1750 rpm, 60 hz
Hide thumbs Also See for Barnes SE51 Series:

Advertisement

Quick Links

Submersible Sewage Ejectors
IMPORTANT!
Read all instructions in this manual before operating pump.
As a result of Crane Pumps & Systems, Inc., constant product improvement program,
product changes may occur. As such Crane Pumps & Systems reserves the right to
change product without prior written notifi cation.
A Crane Co. Company
420 Third Street
Piqua, Ohio 45356
Phone: (937) 778-8947
Fax: (937) 773-7157
www.cranepumps.com
Manual Index
BARNES
BARNES
INSTALLATION MANUAL
Series: SE51 & SE52
.4Hp, 1750 RPM, 60 Hz.
83 West Drive, Bramton
Ontario, Canada L6T 2J6
Phone: (905) 457-6223
Fax: (905) 457-2650
®
Form No. 027277-Rev. G

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Barnes SE51 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Crane Barnes SE51 Series

  • Page 1 Read all instructions in this manual before operating pump. As a result of Crane Pumps & Systems, Inc., constant product improvement program, product changes may occur. As such Crane Pumps & Systems reserves the right to change product without prior written notifi cation.
  • Page 2: Table Of Contents

    SEAL TOOL KIT (see parts list) PRESSURE GAUGE KIT (see parts list) Other brand and product names are trademarks or registered trademarks of their respective holders. ® Barnes is a registered trademark of Crane Pumps & Systems, Inc. 1988, 2002, 4/2006, 8/06 Alteration Rights Reserved...
  • Page 3: Safety First

    Crane Pumps & Systems, Inc. is not responsible for WARNING ! Do not pump hazardous materials losses, injury, or death resulting from a failure to observe (fl...
  • Page 4: Pump Specifications

    Manual Index PUMP SPECIFICATIONS SERIES: DISCHARGE ......2” NPT, Female, Vertical UPPER BEARING ......Sleeve, Oil Lubricated LIQUID TEMPERATURE ..104°F (40°C) Continuous LOWER BEARING .....Single Row, Ball, Oil Lubricated VOLUTE ........Cast Iron ASTM A-48, Class 30 MOTOR: Design ....NEMA L Torque Curve, Oil Filled, MOTOR HOUSING ....Cast Iron ASTM A-48, Class 30 Squirrel Cage Induction SEAL PLATE ......Cast Iron ASTM A-48, Class 30...
  • Page 5: General Information

    Barnes representative or Crane Pumps & Systems Service Department in Piqua, Ohio, telephone C-3) Liquid Level Controls: (937) 778-8947 or Crane Pumps & Systems Canada, Inc., The level controls are to be supported by a mounting Bramton, Ontario, (905) 457-6223.
  • Page 6 Manual Index Automatic Manual FIGURE 3 Automatic - Plug fl oat cord into GFI outlet, then plug pump cord into fl oat cord. Manual - Plug pump cord directly into GFI outlet. C-4) Electrical Connections: An acceptable motor control switch shall be provided at the time of installation.
  • Page 7: Start-Up Operation

    Manual Index MODEL NO VOLT/ NEMA FULL LOCKED CORD CORD CORD WINDING (Nom) START LOAD ROTOR SIZE TYPE RESISTANCE CODE AMPS AMPS inch (mm) MAIN - START SE51 115/1 1750 11.6 18.4 14/3 SJTOW 0.390 (9.9) 1.34 -- 16.88 SE52 230/1 1750 10.5...
  • Page 8 Manual Index F-1.2) Testing Oil: 1.) Place pump on it’s side, remove pipe plug (41), from motor housing (11) and drain oil into a clean, dry container. 10 PSI AIR 2.) Check oil for contamination using an oil tester with a range to 30 Kilovolts breakdown.
  • Page 9 Manual Index Position unit upright, using blocks to avoid resting unit on Seal - Remove rotating member (1a), spring (1c) and shaft. Remove gland nut (12b), friction rings (12c) and retaining ring (1d) from shaft. (see Figure 5). Examine all seal grommet (12d) from motor housing (11), see Figure 8.
  • Page 10 Manual Index Seal - Clean and oil seal cavity in lower end bell (10). Press Insert capacitor (18) in bracket (17), attach motor leads with stationary member (1a) fi rmly into lower end bell (10), using fl ag terminals to capacitor and place terminal boot (15) over a seal pusher (see parts list - seal tool kit), nothing but the terminals.
  • Page 11: Replacement Parts

    Manual Index G-2 PART NUMBER: The part number consists of a six (6) digit number, which appears in the catalog. A one or two letter suffi x may follow this number to designate the design confi guration. This FIGURE 9 number is used for ordering and obtaining information.
  • Page 12: Trouble Shooting

    Manual Index TROUBLE SHOOTING CAUTION ! Always disconnect the pump from the electrical power source before handling. If the system fails to operate properly, carefully read instructions and perform maintenance recommendations. If operating problems persist, the following chart may be of assistance in identifying and correcting them: MATCH “CAUSE”...
  • Page 13: Cross-Section (Fig. 10)

    Manual Index FIGURE 10...
  • Page 14: Exploded View (Fig. 11)

    Manual Index FIGURE 11...
  • Page 15: Parts List

    Manual Index PARTS KITS Seal Kit ......P/N: 085204 (†) 1, 6, 8, 12c, 23, 24, 29, 31, 32 Overhaul Kit ..... P/N: 085207 (◊) 1, 6, 12c, 16, 19, 21, 23, 24, 29, 31, 32, 33 Seal Tool Kit ..... TL: 21355 Pressure Gauge Kit ..
  • Page 16: Return Goods Policy

    RETURNED GOODS RETURN OF MERCHANDISE REQUIRES A “RETURNED GOODS AUTHORIZATION”. CONTACT YOUR LOCAL CRANE PUMPS & SYSTEMS, INC. DISTRIBUTOR. Products Returned Must Be Cleaned, Sanitized, Or Decontaminated As Necessary Prior To Shipment, To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material.
  • Page 17: Start Up Report

    This form is designed to provide assurance that customer service and a quality product are the number one priority with Crane Pumps & Systems, Inc (CP&S). Please fi ll out the following questions as completely and accurate as possible. When complete, mail this form to: In U.S.A Send To:...
  • Page 18 Manual Index CP&S control panel part no. and brand Number of pumps operated by control panel NOTE: At no time should holes be made in top of control panel, unless proper sealing devices are utilized. Control panel manufactured by others Company name Model number Short circuit protection...
  • Page 19: Warranty Registration

    Your product is covered by the enclosed Warranty. Complete the Warranty Registration Form and return to Crane Pumps & Systems, Inc. Warranty Service Group If you have a claim under the provision of the warranty, contact your local Crane Pumps & Systems, Inc. Distributor.
  • Page 20 Manual Index FOLD HERE AND TAPE, DO NOT STAPLE PLACE STAMP HERE CRANE PUMPS & SYSTEMS, INC. WARRANTY SERVICE GROUP 420 THIRD STREET PIQUA, OHIO 45356 - U.S.A.