Setra Systems Multi-Sense 260 Series Installation Manual

Multi-range differential pressure transducer

Advertisement

Quick Links

MECHANICAL INSTALLATION

Mounting Position

Mount and calibrate in vertical position for quick and easy installa-
tion on ducts, walls or ceilings and in control rooms.

Media Compatibility

Model 260 transducers are designed to be used with air or
nonconducting gases.
Use with liquids or corrosive gases will damage the unit.

Environment

The operating temperature limits of the 260 are as follows:
Operating Temperature
Compensated Temperature Range

SIMPLE 5-STEP SETUP INSTRUCTIONS -

STEP 1
For CE compliance a properly grounded shielding cable is
required.

ELECTRICAL CONNECTIONS

Rem ovable T erm inal Block for Easy Wiring
STEP 1: Wire and Power Up Unit - Follow diagrams
below for 2-wire and 3-wire configurations. After
completing wiring requirements - Apply power to
the Model 260.
Multi-Sense Voltage
3-Wire, 0-5, 0-10 VD C C onfiguration
Model 260
24V AC/DC
EXC
COM OUT
Nominal
Excitation
+
-
+
Power
Supply
-
13 - 30V
Multi-Sense C urrent
2-Wire, 4-20 m A C onfiguration
Model C260
24V (DC Only)
EXC
COM OUT
Nominal
Excitation
-
+
+
Power
Supply
-
13 - 30V
Installation Guide
"Multi-Sense" Model 260 Series
Multi-Range Differential Pressure Transducer
32°F to 122°F (0°C to 50°C)
32°F to 122°F (0°C to 50°C)
+
+
Voltage
-
Monitor
X
Typical 250 Ohm
+
Current
Sense Resistor
-
Monitor
for 1-5V Output
Measurement

GENERAL INFORMATION

Every Model 260 has been calibrated and tested before shipment to guarantee
performance for all pressure ranges.
The Model 260 is available in four versions, which have field selectable range
capability via a slide switch. See four versions below:

MULTI-SENSE RANGE SPECIFICATIONS

Version
Unidirectional
Model MS1
0.1" , 0.25" , 0.5" and 1.0" W .C . FS
Model MS2 1.0" , 2.5" , 5.0" and 10" W .C . FS
Model MS3
25, 50, 100 and 250 Pa FS
Model MS4 .25, .50, 1.00 and 2.5 kPa
The Model 260 is available in three field selectable output configurations. See three
versions below:
2-Wire
4-20 m A (C urrent)
3-Wire
0-5, or 0-10 VD C (Voltage)
SIMPLE 5-STEP SETUP INSTRUCTIONS - STEPS 2 - 5
Power On - LCD Display
Display momentarily toggles thru all existing setup parameters on initial power
up. Pressure is normally indicated on display. Units are either in inches of water
column (WC) MS1 & MS2, or Pascal (Pa) MS3 & MS4.
*STEP 2: Select Pressure Range: Set
appropriate full scale range using
the Slide Switch Multiplier. LCD
will momentarily indicate selected
range.
STEP 3: Select Unidirectional
or Bi-directional mode.
**STEP 4: Select Current (mA)
or Voltage 0-5, or
0-10 VDC output range.
*Step 2 will follow same
instructions for other inches of
water column and pascal
ranges.
* * Step 4 be sure to set mA/volt
switch to volt position if using
0 to 5 or 0 to 10V outputs

ZERO AND SPAN ADjUSTMENT*

The unit may be recalibrated in the field using the push button zero/span.
Zero Adjustment:
1. With unit at zero differential pressure, push zero button for 5 seconds. Units
output and display will update.
Span Adjustment:
2. Apply full scale pressure (Note: Full scale value of largest range.). Press and hold
zero button for 5 seconds. Units output and display will update.
*Zero and Span points must be within 10% of factory setting.
Ranges
Bidirectional
+/- 0.1" , 0.25" , 0.5" and 1.0" W .C . FS
+/- 1.0" , 2.5" , 5.0" and 10" W .C . FS
+/- 25, 50, 100 and 250 Pa FS
+/- .25, .50, 1.00 and 2.5 kPa
RANGE:
1 0.5 0.25 0.1
STEP 5: Push Button
UNI/BI
ZERO
Zero - While at
● ● ●
zero pressure
JUMPER
Press and hold
mA/Volt
the Zero Push
Button for 5
seconds to auto-
5V/10V
matically reset
● ● ●
output to zero.
JUMPER
+
-
+
EXC COM OUT
2601MS1
S/N:
Date Code

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Multi-Sense 260 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Setra Systems Multi-Sense 260 Series

  • Page 1 Installation Guide “Multi-Sense” Model 260 Series Multi-Range Differential Pressure Transducer GENERAL INFORMATION Every Model 260 has been calibrated and tested before shipment to guarantee performance for all pressure ranges. The Model 260 is available in four versions, which have field selectable range capability via a slide switch.
  • Page 2 No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any other liability in connection with the sale of its products. For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative Hengstler GmbH, Uhlandstr. 49, 78554 Aldingen, Germany (Tel: +49-7424-890, Fax: +49-7424-89500).

This manual is also suitable for:

Multi-sense ms1 seriesMs2Ms3Ms4

Table of Contents