Heater operation when the SeG9 of 02 series installation option is set to using hot water heater or when SeG15 is set to
(*3)
using external heater
e.g. 1) S etting 02 series SEG9 ="1" / Setting 05 series SEG18 = " 0": Hot water heater is turned on at the same time as the
heating thermostat is on, and turned off when the heating thermostat is off .
e.g. 2) S etting 02 series SEG15 ="2" / Setting 05 series SEG18 ="A":
Room temp . ≤ set temp . + f(heating compensation temp . )
- external heater is turned on when the temperature is maintained as 4 . 5  °C for 10 minutes .
Room temp . > set temp . + f(heating compensation temp . )
- external heater is turned off when the temperature is maintained as 4 . 5  °C + 1 °C (1 °C is the Hysteresis for On/
Off selection . ]
Additional information on SeG 3, 4, 5, 6, 8, 9
When the SeG 3 is set as "1" and follow AutoChangeOver for HR only operation, it will operate as below .
Temp .
Ts
Set temp . for Auto mode
❋ ❋ Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SeG9 .
DVM PAC Mirage_IM_05674A-00_EN.indd 31
Standard temp . for
Heating  Cooling
b
Standard temp . for Cooling
d
Standard temp . for
Cooling  Heating
ENGLISH-31
c
C
B
A
D
a
Standard temp . for Heating
A : Set with SeG4(˚C)
B : Set with SeG5(˚C)
C : Set with SeG6(˚C)
D : Set with SeG8(˚C)