ROOM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT AM14A1(B1)E07 UM14A1(B1)E2 AM20A1(B1)E06 UM20A1(B1)E3 AM20A1(B1)E08 Manual SERVICE AIR CONDITIONER CONTENTS 1. Pre c a u t i o n s 2. Product Specifications 3. Operating Instructions and I n s t a l l a t i o n 4.
Page 2
. Fig. 1-3 No Kids Nearby! 1 0 . Be sure to clean the unit and its surro u n d i n g a re a . Fig. 1-4 Clean the Unit Samsung Electronics...
Page 5
And if you need more information, please see the service bulletin Copyright Tr a d e m a r k s Samsung is a registered trademark and ®œ 1995 by Samsung Electronics Co., Ltd. SyncMaster 17GLi/CMG7387L and All rights reserved. MacMaster...
Page 6
8. PCB Diagrams 8-1 Main PCB-INDOOR UNIT 8-1-1 AM14A1(B1)E07 (DB93-10603A) Samsung Electronics...
Page 7
PI0.6 SN T 52MM OP01 DE39-60001A WIRE SO COPER PI0.6 SN T 52MM OP02 DE39-60001A WIRE SO COPER PI0.6 SN T 52MM OP03 DE39-60001A WIRE SO COPER PI0.6 SN T 52MM OP04 DE39-60001A WIRE SO COPER PI0.6 SN T 52MM Samsung Electronics...
COMPRESSOR DRIVE FAN SPEED SELECT • STEPPING MOTOR STEPPING MOTOR DRIVE BLADE-H BUZZER DRIVE BUZZER • MOVING SELECT DC 5V DC 12V VOLTAGE REGULATOR ON, OFF TIMER SELECT TEMPERATURE SELECT SLEEP SELECT TIME SETTING AC INPUT POWER TRANSFORMER Samsung Electronics...
Page 18
Input Indoor unit Simultaneous Indoor unit controller. room 1 and Room B, and SV-B, SV-C room 2 motor room C sensor sensor Room “B” Input Compressor Compressor delay motor circuit SV-C SV-C sensor driver SV-B SV-B Sensor driver Samsung Electronics...
Page 19
6. Exploded Views and Parts List 6-1 Indoor Unit 6-1(a) AM20A1(B1)E08, AM14A1(B1)E07 Samsung Electronics...
Page 27
LABEL DOOR ART 90 PH-M2 SCREW TAP PH-M2 DB67-60061A SPRING BATTERY SUS 304 DB67-60062A SPRING BATTERY SUS 304 DB67-60063A SPRING BATTERY SUS 304 90 X 250 PE BAG 90 X 250 DB93-40179B ASS’Y PCB REMOCON DB61-40243A HOLDER REMOCON Samsung Electronics...
Indoor unit Room sensor Error (open or short) 3 O P E R ATING and TIMER LED blinking (1Hz) Indoor unit heat exchanger temperature sensor Error (open or short) 4 FAN LEA blinking (1Hz) Indoor fan malfunctioning (for spead is Below 38Orpm) Samsung Electronics...
Check PCB pattern. Replace ICO2 Replace main PCB. 10ms Is voltage output terminal of D101~D105(IN4007) normal? Are voltage at #30 and #31 of the micom normal? Replace resonator (X501) 100ns Replace IN4007 Is operation normal? Replace micom Samsung Electronics...
Page 32
Is the voltage at both ends of the C102 Replace the C102 electrolytic condenser in the range of DC16~DC25V? and C104. Is the voltage at both ends of the C104 electrolytic condenser DC12V? Is the IC01(KA7812) normal? Replace the IC01 Samsung Electronics...
Page 33
Is the supply voltage of the fan out of order. be replaced. motor sufficient? Test rod location Normal voltage PCB CN73 Condition Fan operate AC 180V MF-C is out of order Replace MFC Fan motor Fan motor should be replaced. is out of order. Samsung Electronics...
Page 34
“A”Compreessor or outdoor fan-motor replaced 1 NO 2 NO Is the room sensor normal register? 10°C 20°C 30°C 17.96k Ω 12.09k Ω 8.3k Ω YES 3 B Room or C Room operating Proceed to the checking points for the outdoor unit. Samsung Electronics...
Page 35
Are the Q902, Q903 and Q905 in "Turn-on" condition? Does the operation of the Q701 lead to Check and replace the Q701 and relay. activation of the compressor relay (RY71)? (Resistance at both ends of the relay: About 150 ) Replace the "B" compressor. Samsung Electronics...
Page 36
Does operation start when swing button of the remote con- Normal trol unit pushed? Voltage at pin #33-#36 of micom (ICO4) Micom (IC04) is faulty. change?(Squarewave) Volatge at pin #10, #11, #12, #13 of IC05 (KID65003) Driver IC05 (KID65003) is faulty. change?(Squarewave) UP/DOWN louver motor is faulty. Samsung Electronics...
Voltage at PIN #30 of Remocon Micom change? Voltage at collecter of Q601 or Q602 change? Q601(C4375Y) or Q602(C1623Y) is faulty. IR LED(CL-1L5EU) is faulty. Voltage at pin #26 of micom (IC04) change (INDOOR UNIT)? Receiver module is faulty. Micom (IC04) is faulty. Samsung Electronics...
Page 38
IC04 DC7V? resistance (R922, R924). Does the operation of the Q702 lead to Check and replace the Q702 and relay. activation of the SV-BY relay (RY72)? (Resistance at both ends of the relay: 400Ω ) Replace the SV-BY Samsung Electronics...
Page 39
Does the turning on and then Check and replace the Q702 and relay. turning off of the Q702 lead to (Resistance at both ends of the relay: 400Ω) turning off of the SV-BY relay (RY72)? Replace the SV-BY solenoid. 5-10 Samsung Electronics...
Page 40
Q908 under "turn off" condition? Check and replace the D905, D909, and Q703 relay Is the Q703 turned. on, indicating the (Coil resistance at both ends of the relay:about 400Ω) operating of the SV-B relay (RY73)? Replace the SV-B solenoid valve 5-11 Samsung Electronics...
Page 41
Is the Q704 turned on, indicating the operating condition Check and replace the D906, D910, and Q704 relay of the SV-C relay (RY74)? (Coil resistance at both ends of the relay : about 400Ω) Replace the SV-C solenoid valve 5-12 Samsung Electronics...
Page 42
• Check and replace the Q703, and Q704. turned off when the Q703 and Q704 are • Check and replace the relay when necessary. turned off. (Resistance at both ends of the relay: About 400Ω) Replace the SV-B and SV-C solenoids. 5-13 Samsung Electronics...
The parts should be replaced in the following pro c e d u re . Check for any faulty part. Detach the faulty part. Replace it with a new part. Check the operation of the new part. The repair is completed. 5-14 Samsung Electronics...
Page 44
1. Indoor unit fan motor is faulty. RMC switch pushed. above 180V~ 1. [FAN] mode 2. Fan speed [Hi] 2. Indoor unit fan motor does not operate. 2. Poor connection of indoor fan motor 3. Continuously operation and connector of RPM sensing (CN43) 5-15 Samsung Electronics...
∞, O Ω … open or short Abnormal Measure resistance between red wire and each terminal. Stepping Motor Normal Approx. 380Ω at ambient temperature (20°C ~30°C) (UP/DOWN swing motor) ∞, O Ω … open or short Abnormal 5-16 Samsung Electronics...
7) Pull the upper left and right of discharge softly for the outside cover to be pulled out. 8) Pull softly the lower part of discharge and push it Caution: Assemble the front panel and fix the hooks of left and right. Samsung Electronics...
Page 47
2) Take all the connector of PCB upper side out. 3) Separate the outdoor unit connection wire from the terminal block. 4) If pulling the Main PCB up, it will be taken out. (Separate the TRANS hook, it before). Samsung Electronics...
Page 48
2) Loosen the fixing two screws and separate the motor holder. 3) Loosen the fixing screw of motor fan. (By use of M3 wrench) Separate the motor from the fan. Separate the fan motor the left holder bearing. Samsung Electronics...
<UM20A1(B1)E3> <UM14A1(B1)E2> 1) Do Procedure above. Fan Motor & Propeller Fan 2) Remove the nut flange. (Turn to the right to remove as it is a left turned screw) 3) Disassemble the propeller fan. <UM20A1(B1)E3> Samsung Electronics...
Without regard to ON/OFF condition in remote controller, use this button to set current time. TIME Adjust the current time using button. (Data can be transmitted after setting up the time) Samsung Electronics...
Page 51
6. FAN SPEED : Manual (3 step), Auto (4 step) * P rotective function : Low temperature Fan speed automatically varies depending release. (Prevention against fre e z e ) on both the diff e rence between setting and the room temperature . Samsung Electronics...
Page 52
The LCD also displays the time re m a i n i n g . select, the compulsory operation mode, buzzer is sounded "beep" 1 0 . 24-Hour ON/OFF Real Setting Ti m e r. : The air conditioner is turned ON at a specified time using ON TIMER Samsung Electronics...
Page 53
(About when the indoor unit room "C" is turned 2 minutes + 3 0 seconds). o n . •Both of the SV-B and SV-C solenoid valves operate when all of the indoor unit room B Samsung Electronics...
Page 54
Outdoor unit power supply Delay of 3 minutes Indoor unit room "B" Delay of 3 minutes Indoor unit room "C" About 2 minutes About 2 minutes Compressor Outdoor fan motor SV-BY SV-B (room"B" soldnoid valve) SV-C (room"C" soldnoid valve) Samsung Electronics...
Page 55
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice. Samsung Electronics...
B Drain hose installation Cut the piping hole sloped slightly Remote control holder Remote control Outdoor unit check point UNIT-A UNIT-B UNIT-C Piping (Liquid) 1/4” Clamper tube Piping (Gas) 3/8” Installation plate Installation tube Pipe-connection Vinyl tape Screw Putty Drain hose Samsung Electronics...
Page 57
Result : All inert gas escapes from the indoor unit. • To prevent dirt or foreign objects from getting into the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping. Samsung Electronics...
Page 58
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as shown in the illustrations above. The hose will be fixed permanently into position once Shield the whole installation has been tested for gas leaks; refer to page 16 for further details. Drain hose Extension drain hose Samsung Electronics...
Page 60
100 ohms (existing grounding electrode) 2 . Use of a grounding electro d e . Grounding screw hole • Specifications of grounding electro d e . Carbon plastic Steel core PVC-insulated wire(2mm x3.5m), green Terminal, M4 3-11 Samsung Electronics...
Page 61
C a u t i o n : Burrs not removed may result in leakage of gas. 90° Oblique Raughness Burr Pipe Reamer 3 ) Insert a flare nut into the pipe and modifty flare . Outer diameter A(mm) ø6.35mm ø9.52mm * Unproper flaring Inclined Surface Cracked Uneven damaged thickness 3-12 Samsung Electronics...
Page 62
18N . m with a torque wrench. 7. Check for gas leakage. - At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap. 3-13 Samsung Electronics...
Page 63
5. Stop operation of the air conditioner. 6. Disconnect the charge hose of manifold gauge. 7. Close the cap of each valve. INDOOR A-UNIT INDOOR B-UNIT 3-2-2(i) Flare unt fixing torque Torque (kg-cm) Outter diameter Fixing Torque Final Torque ø6.35(Liquid Side) ø9.52(Gas Side) 3-14 Samsung Electronics...
Page 64
7. Move the indoor and outdoor units to a new plug to avoid foreign material entering. l o c a t i o n . 8. Remove the mounting plate for the indoor unit and move it to a new location. 3-15 Samsung Electronics...
Page 65
Vo l t a g e / F requency : 240V/50Hz Cooling Capacity & Air Outlet Temperature Cooling Capacity Air Outlet Temp. 10000 9000 8000 7000 21/15 27/19 35/24 43/26 Outdoor Temperature(DB/WB) Current & Low Pressure Current Low Pressure 21/15 27/19 35/24 43/26 Outdoor Temperature(DB/WB) 3-16 Samsung Electronics...
MRA12030-12008 MRA12037-12007 MRA12054-12008 Standard Conditions ISO R5151 Standard ISO R5151 Standard • The basic performance test is based on the piping of 5MT.(Be sure to check the installing conditions as extension of the piping may lead to performance degradetion.) Samsung Electronics...
Page 68
2-2 Dimensions 2-2-1(a) Indoor Unit (AM14A1(B1)E07/AM20A1(B1)E08) (Remote control) (Front view) Air out Installation plate (Rear view) 2-2-1(b) Indoor Unit (AM20A1(B1)E06) (Remote control) (Front view) (Rear view) Samsung Electronics...
Piping Temp.(°C) Temp. Condition (°C) Operating Condition (kg/cm Indoor Outdoor 3-way valve Standard 5.0~5.2 A or B Max over load 6.0~6.3 Cooling Low temp. 3.4~3.6 Standard 5.0~5.2 A + B Max over load 6.0~6.3 Low temp. 3.4~3.6 (Pipe Length:5m) Samsung Electronics...