Option
SeG19
explanation
Page
Remote
controller
-
display
Indication Details
Indication
and Details
3
Minimizing fan operation when thermostat is off
(*1)
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode .
When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will
(*2)
not be output .
2: Fan is turned on continually when the external heater is turned on,
3: Fan is turned off when the external heater is turned on with cooling only indoor unit
Cooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fi x it as
cool mode .
❋ ❋ I f Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or
wired remote controller sensor to detect indoor temperature exactly .
Default setting value
(*3)
- 4Way Cassette, Mini 4Way Cassette: 5 °C
- Other indoor units: 2 °C
This function can be applied to 4 Way Cassette and Mini 4 Way Cassette only . If the air conditioner operates the heating
(*4)
mode immediately after fi nishing the cooling mode, the condensated water in the drain pan becomes water vapor by the
heat of the indoor unit heat exchanger . Since the water vapor might be condensed on the indoor unit, which may fall into
a living space, use this function to get rid of the water vapor out of the indoor unit by operating the fan (for maximum
20 minutes) even when the indoor unit is turned off after cooling mode is turned to heating mode .
• Do not install the electronic heater in the fl ow channel of the indoor unit fan .
electronic heater should not
CAUTION
be installed .
Setting an indoor unit address and installation option
DVM PAC Mirage_IM_05674A-00_EN.indd 27
SeG20
SeG21
Heating setting compensation /
Individual control of
Removing condensated water in heating
a remote controller
mode
Indication
Details
Indication
Heating Setting
Compensation
0
Default 
0 or 1
Channel 1
1
2 °C
2
Channel 2
2
5 °C
3
Channel 3
3
Default 
4
2 °C
4
Channel 4
5
5 °C
Discharge side
Suction side
Air Flow
Duct Indoor unit
ENGLISH-27
SeG22
eeV Step of stopped unit
during oil return/defrost
mode
Details
Removing
Indication
Details
Condensated
Water in Heating
Mode
Default
(*3)
Disuse
0
value
Disuse
Disuse
Oil return
Use 
(*3)
(*4)
or noise
1
decreasing in
Use 
(*4)
defrost mode
Use 
(*4)
SeG23
SeG24
-
Louver Swing Speed
-
Indication Details Indication
Details
0
Default 18 ms
1
27 ms
2
24 ms
3
21 ms
-
4
18 ms
5
15 ms
6
12 ms
7
9 ms