Function Selection
When a checkup detection object is inserted along the beam center line mark ( mark ) so that it should
interrupt beams, the sensor must be under interrupted status (all 5 incident light level indicators turn OFF,
and the OFF output indicator turns ON). Detection must be checked for 3 points shown below:
• Right in front of an emitter (A)
• Right in front of a receiver (B)
• In the middle of an emitter and a receiver (C)
When the external test function is used:
The OFF-state indicator turns ON when the test input line is short-circuited to 9V to Vs.
When the external device monitoring function is used:
When the F3SJ-AM is blocked and the external device monitoring input terminal is open, it enters a lock-
out state.
When the start interlock function is used:
After the F3SJ-AM is turned ON, the OFF-state indicator remains turned ON, even if the F3SJ-AM is
receiving light. The reset switch input turns ON the ON-state indicator.
When the restart interlock function is used:
While the ON-state indicator is ON, the OFF-state indicator remains turned ON, even when the F3SJ-AM
is blocked and then receives light again. The reset switch input turns ON the ON-state indicator.
When muting function is used, minimum muting time limit required must be set.
When muting function's operation mode is exit only muting mode, minimum muting waiting time required
must be set.
Under muting state, a signal that indicates muting state must be output from either of the followings:
• External Indicator 1 or 2
• Auxiliary Output 1
When override function is used, minimum override time limit required must be set.
Under override state, a signal that indicates override state must be output from either of the followings:
• External Indicator 1 or 2
• Auxiliary Output 1
-Checking that Hazardous Parts Stop While the Machine Operates
The hazardous parts stop immediately when a checkup detection object interrupted any beam at 3 posi-
tions: "directly in front of the emitter", "directly in front of the receiver", and "between the emitter and
receiver".
The hazardous parts remain stopped as long as the checkup detection object keeps interrupting a beam.
The hazardous parts stop when the power of the F3SJ-AM is turned OFF.
The actual response time of the whole machine is equal to or less than the calculated value.
Maintenance Checklists
To ensure safety, keep a record of the inspection results. When the user is a different person from those who
installed or designed the system, he/she must be properly trained for maintenance.
Checklists
-Inspection at Startup and When Changing Operators
There is no approach route other than through the detection zone of the F3SJ-AM.
Part of the operator's body always remains in the detection zone of the F3SJ-AM when working around
the machine's hazardous part.
The actual safety distance is equal to or greater than the calculated value.
11