10 Maintenance
Fig.73
2
Fig.74
3
Fig.75
4
Fig.76
5
84
10.5.1
1. Switch off the appliance and close the valves for the heating circuits
on the plate.
2. Remove the magnet from the filter.
The magnetic particles stuck inside the filter will drop to the bottom
and be ejected via the drain.
MW-1001305-1
3. Connect a pipe to the filter valve, then open the valve by a quarter
turn.
MW-1001306-1
4. Once the water running out of the pipe is clear, re-close the valve. If
necessary, open and close the valve several times to create surges,
and clean the filter better.
MW-1001307-1
5. Refit the magnet. Pushing it in fully.
MW-1001308-1

Magnetic filter annual maintenance