The CPV Direct contains electronically sensitive compo­
nents. The CPV Direct will be damaged if you touch the
contact surfaces of the plug connectors and if you do
not observe the regulations for handling electrostati­
cally sensitive components.
Proceed as follows when configuring:
1. Switch off the power supply.
2. Remove the switch module.
3. Set the following with the DIL switches: field bus pro­
tocol, extension to the CP system, field bus address/
station number, diagnostic mode (only PROFIBUS or
ABB CS31), baud rate (only Festo field bus).
4. Refit the switch module.
5. If the CP system is the first or last slave in a field bus
segment, the terminating resistor in the Festo Sub-D
plug must be activated.
Warning
S Make sure that switch-on test pulses are sup­
pressed/switched off when you operate the CPV
Direct via a "safety I/O module".
S Check the measures required for putting your system
into a safe status in the event of an EMERGENCY
STOP.
Further information can be found in manual
P.BE-CP-DI01-.. .