Interior Installation With Cathedral Ceiling - DuraVent DURATECH PREMIUM Installation And Operation Instructions Manual

Factory-built 650c chimney 6”, 7”, & 8” dia
Table of Contents

Advertisement

4

INTERIOR INSTALLATION WITH CATHEDRAL CEILING

SQUARE SUPPORT (CS24)
REDUCED CLEARANCE SUPPORT (RCS)
NOTE: The Reduced Clearance Sup-
port comes with a collar. It can be
discarded for this application.
Step 1: Locate the chimney in a
convenient location as near
as possible to the appliance
outlet. Cut and frame an
opening in the roof for the support. The sides
of this frame must be vertical.
See Figure 11
Step 2: From below, push the Support into the
framed opening in the ceiling.
NOTE: The bottom portion of the support must
project below the ceiling to ensure appropriate
clearances to stovepipe. See Table 6.
Step 3: Using a level, make sure the support is ver-
tical. If the support extends above the roof,
cut it flush with the top of the roof. Nail the
support to the framed opening using (12)-3"
spiral nails or #8 x 1 1/2" wood screws.
See Figure 10
Step 4: Place first chimney length into the support.
Twist to lock into place. Wrap the insulation
pad (RCS) around the chimney, then slide it
down within the support box. Make sure the
insulation makes contact with the bottom of
the support. Additional pieces of insulation
can be loosely tucked down within corners.
Do not compress insulation, this reduces
effectiveness.
With a Square Support (CS24) or in steeper
cathedral applications where a extra box
length is required, additional insulation may
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
FLASHING
FINISH TRIM
(12) 3" lg. SPIRAL NAILS or
1 1/2" WOOD SCREWS
INSULATION
Figure 10
HOLE SIZE
DOWN
SIDES OF HOLE MUST
ACROSS
BE VERTICAL
SLOPE
A
Figure 11
REDUCED CLEARANCE SUPPORT (RCS)
FRAMED OPENING REQUIREMENT
(Cathedral support (CS24) dimensions are the same for all
diameters. Use 8'' size reference for the frame opening)
Chimney
6"
Size
Roof
A
B
Slope
x/12
0
12-1/8 12-1/8 13-1/8
2/12
12-1/8 12-1/4 13-1/8
4/12
12-1/8 12-3/4 13-1/8
6/12
12-1/8
13-1/2
8/12
12-1/8 14-1/2 13-1/8
10/12
12-1/8 15-7/8 13-1/8
12/12
12-1/8 17-1/8 13-1/8
NOTE: ALL DIMENSIONS ARE IN INCHES.
Table 5
RAIN CAP (VC)
SILICONE
CAULKING
STORM COLLAR (SC)
RAFTER
REFER TO TABLE 6
SUPPORT
(RCS)
ROOF SLOPE
INCHES
12 IN
B
X
7"
8"
A
B
A
13-1/8
14-1/8
14-1/8
13-1/4
14-1/8
14-3/8
13-7/8
14-1/8
14-7/8
13-1/8
14-5/8
14-1/8
15-7/8
15-3/4
14-1/8
16-7/8
17-1/8
14-1/8
18-1/2
18-1/2
14-1/8
B
20