LED Diagnostics:
Red (DC)
Green (AC)
ON
ON
ON
OFF
OFF
ON
OFF
OFF
Terminal Identification:
Terminal
Function/Description
Legend
L, G, N
Connect 115 VAC to these terminals:
L to Hot, N to Neutral, G to ground.
+ DC -
12 / 24VDC 4 amps continuous power limited output.
AC FAIL
Used to notify loss of AC power, e.g. connect to audible device or alarm
N.O., C, N.C.
panel. Relay normally energized when AC power is present.
Contact rating 1 amp @ 115VAC / 28VDC
Low Battery
Used to indicate low battery condition, e.g. connect to alarm panel.
N.O., C, N.C.
Relay normally energized when DC power is present.
Contact rating 1 amp @ 115VAC / 28VDC
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.
- BAT +
Stand-by battery connections. Maximum charge rate .5 amp.
OFF
ON
L
G
N
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Made in U.S.A.
Power Supply Status
Normal operating condition
Loss of AC, Stand-by battery supplying power
No DC output
Loss of AC. Discharged or no stand-by battery. No DC output.