Accessories For The On-Site Pellet Store - Viessmann VITOFLEX 300-UF Technical Manual

Solid fuel boiler 390 to 1250 kw
Table of Contents

Advertisement

Fuel storage
(cont.)
Window installation with screws
A plate is set into the window opening. The connector is fitted
through the plate, secured with screws and earthed with a pipe clip.
B
A
A Fill connector
B Screws
C Pipe clip for earthing
D Outlet Ø 110 mm
E Window opening
Installation in the light well
The following types of installation are possible:
■ Into the wall
■ Into the window opening
The shortened fill and return air connectors are each inserted into a
45° bend. Insert the bend into the extension pipe that passes
through the wall or window opening.

Accessories for the on-site pellet store

Baffle mat 1.42 x 1.25 m
For part no., see pricelist
The baffle mat consists of a 4.0 mm thick pressed rubber mat with
fibre-reinforcement for high strength.
Install baffle mat B with a clearance of at least 200 mm from the
wall opposite the fill connector. The baffle mat protects the wood pel-
lets, the brickwork and the plaster/render.
Pieces of plaster/render or wall that have been knocked off can hin-
der the pellet supply or block the ash removal from the boiler.
Standard delivery
■ Baffle mat 1.42 x 1.25 m
■ Section anchor with carbine fastening
VITOFLEX 300-UF
C
D
E
B
A
E
A Fill connector
B Pipe clip for earthing
C Extension pipe
D Wall duct Ø 110 mm
Or
Outlet Ø 110 mm
E 45° bend
C
D
7
Viesmann
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitoflex 300-rf

Table of Contents