Sizing The Expansion Vessel - Viessmann VITOFLEX 300-UF Technical Manual

Solid fuel boiler 390 to 1250 kw
Table of Contents

Advertisement

Design information
Heating water buffer cylinder
D
More than 1 heating water buffer cylinder as low loss header
E
(5 sensors)
Heating water buffer cylinder 2
F
Heating water buffer cylinder 1
G
Low loss header
H
Possible with large water volume in mains
TS131
L
(2 pce from Vitoflex 300-UF, 720 kW)
Design recommendation
Trade name
9
Rated heating output
Boiler circuit
Thermally activated safety valve TS-131
Required water flow rate at 2.5 bar
Cylinder capacity
Supply line ZLg
Supply line ZLv
Drain line ALv
Safety valve type SV 68 M
Safety line SL

Sizing the expansion vessel

In accordance with EN 12828, water heating systems must be equip-
ped with a diaphragm expansion vessel. The size of the expansion
vessel to be installed is subject to the heating system specification
and should be checked in each case.
Quick selection table for calculating the vessel size V
Safety valve
bar
p
sv
Pre-charge
bar
pressure
System vol-
litre
ume V
A
Selection example
Conditions:
p
= 3 bar (response pressure of the safety valve)
sv
H
= 13 m (static head of the system)
Q
= 18 kW (rated heating output of the heat source)
v
= 8.5 l/kW (specific water capacity)
Panel radiators 90/70°C
V
= 1000 l (volume of buffer cylinder)
PH
Conversion factors for alternative flow temperatures other than 90 °C
Flow temperature °C
Conversion factor
Divide the vessel size found in accordance with the above tables by the conversion factor.
Viesmann
90
(cont.)
kW
pce
l/h
l
R
R
R
R
n
3.0
1.0
1.5
1.8
220
340
200
510
320
200
840
440
260
1050
540
330
1470
760
460
2100
1090
660
2630
1360
820
3150
1630
990
4200
2180
1320
5250
2720
1650
6300
3260
1980
8400
4350
2640
10500
5440
3300
50
55
60
3.03
2.50
2.13
Additional heat generator controlled with a max. retaining
M
valve for
- Oil/gas boiler
- Electric heater
With additional heat generator, dual mode
P
- Oil, gas, electric
M20 Boiler circuit pump
Y20 Boiler mixer
KW Cold water supply min. 2.5 bar, max. 3.5 bar
Vitoflex 300-UF
390
530
DN 80
DN 80
1
1
1637
2224
3200
4300
¾
¾
¾
¾
¾
¾
DN 50
DN 65
The specific water capacity v was determined as follows:
■ Radiators: 13.5 l/kW
■ Panel radiators: 8.5 l/kW
■ Underfloor heating system: 20 l/kW
Calculation:
V
= Q x v + 1000
V
A
n
V
= 18 kW x 8.5 l/kW + 1000 l
A
= 1153 l
litre
25
If possible, when calculating the gas pre-charge pressure, select a
35
supplement of 0.2 bar:
50
p
≥ H/10 + 0.2 bar
80
0
p
≥ (13/10 + 0.2 bar) = 1.5 bar
100
0
140
From the table:
200
With p
= 3 bar, p
= 1.5 bar, V
250
sv
0
V
= 250 l (for V
max. 1360 l)
300
n
A
400
Selected:
500
1 x diaphragm expansion vessel N 250 (from Vitoset pricelist)
600
800
■ All details relate to a flow temperature of 90 °C.
1000
■ The tables have allowed for a hydraulic seal to DIN 4807-2.
Recommendation:
■ Select a sufficiently high safety valve response pressure:
p
≥ p
+ 1.5 bar
sv
0
■ For circulation pumps, due to the inlet pressure required, select at
least 0.3 bar above the pre-charge pressure even for attic installa-
tions: p
≥ 1.5 bar
0
■ Set the fill or starting pressure on the water side of vented systems
in their cold state at least 0.3 bar above the pre-charge pressure:
p
≥ p
+ 0.3 bar
F
0
65
70
75
1.82
1.59
1.39
1.24
720
950
DN 100
DN 125
2
2
3020
3986
5800
7600
1
1
¾
¾
¾
¾
2x 1½
DN 80
2x DN 65
= 1153 l
A
80
85
90
1.11
1.00
0.90
VITOFLEX 300-UF
1250
DN 125
2
5246
10000
¾
¾
2x 1½
2x DN 80
95
100
0.82