Pentair T Series Instruction Manual
Hide thumbs Also See for T Series:

Advertisement

Quick Links

T-SERIES
Air Conditioner
t62 Model
INSTRUCTION MANUAL
Rev. E
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx
© 2013 Pentair Equipment Protection
P/N 10-1008-239
88047465

Advertisement

Table of Contents
loading

Summary of Contents for Pentair T Series

  • Page 1 T-SERIES Air Conditioner t62 Model INSTRUCTION MANUAL © 2013 Pentair Equipment Protection 88047465 Rev. E P/N 10-1008-239 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 2: Table Of Contents

    LIMITATION OF LIABILITY ................................15 NOTE: Some of the information in this manual may not apply if a special unit was ordered. If additional drawings for a special unit are necessary, they have been inserted. Contact Pentair Equipment Protection if further information is required.
  • Page 3: Receiving The Air Conditioner

    Damage evident upon receipt should be noted on the freight bill. Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -- within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with the delivering carrier.
  • Page 4: Installation Instructions

    3. 1 = 115 Volt, 2 = 230 Volt, 4 = 460 Volt. 4. 6 = 50/60 Hz or 60 Hz only. 5. Unique set of numbers for each air conditioner which identifies the accessories on a model. © 2013 Pentair Equipment Protection 88047465 - 4 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com...
  • Page 5: Dimensional Drawing

    Mounting Gasket kit, 62-1000-50 included. air conditioner Apply gasket to back of air conditioner before mounting to enclosure. CUTOUT INSTRUCTIONS (As viewed from outside of enclosure) © 2013 Pentair Equipment Protection 88047465 - 5 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 6: Technical Information

    At temperatures between 70-100 F the yellow LED is lit and the fan is being regulated under full speed. • At temperatures above 100 F the green LED is lit and the fan is operating at full speed. © 2013 Pentair Equipment Protection 88047465 - 6 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com...
  • Page 7: Contactor

    49.6 54.4 339.9 306.1 72.2 56.2 57.2 362.4 328.2 80.2 63.2 351.4 88.7 70.7 62.8 410.7 375.9 97.8 78.8 65.6 436.5 401.7 12.8 107.5 87.5 © 2013 Pentair Equipment Protection 88047465 - 7 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 8: Unit Characteristics

    Evaporator Delta Condenser Delta Unit Amps In (°F) Pressure (psi) Pressure (psi) (°F) (°F) 65-80 10-12 45-75 175-225 15-25 18-28 80-100 11.5-15 60-100 210-320 15-25 18-28 © 2013 Pentair Equipment Protection 88047465 - 8 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 9: Wire Diagram

    WIRE DIAGRAM © 2013 Pentair Equipment Protection 88047465 - 9 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 10: Service Data

    Controller, Head Pressure 10-1106-108 Evaporator Outlet Filter (Optional) 10-1000-01 Filter/Dryer 52-6028-09 Grille, Condenser fan 13-1014-03 Switch, Dual Pressure 52-6104-59 Thermal Expansion Valve 10-1040-46 Transformer 10-1006-143 Thermostat 10-1061-16 © 2013 Pentair Equipment Protection 88047465 - 10 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...
  • Page 11: Maintenance

    CAUTION Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteriorate condenser coils, blowers and motors, etc. Contact Pentair Equipment Protection for special recommendations. REFRIGERANT LOSS Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks.
  • Page 12: Trouble Shooting

    (replace control box cover for safety). This will activate the switch in the thermostat. Turn the power on and if both fans and the compressor come on, the thermostat needs to be replaced. © 2013 Pentair Equipment Protection 88047465 - 12 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com...
  • Page 13: Symptoms And Possible Causes

    Getting water in enclosure Enclosure not sealed (allowing humidity in) Mounting gasket damaged For additional technical information (i.e., amp draw, pressures, temperatures) , contact Pentair Equipment Protection at 800-896-2665. © 2013 Pentair Equipment Protection 88047465 - 13 - RSPSupply - 1-888-532-2706 - www.RSPSupply.com...
  • Page 14: Warranty

    Pentair Equipment Protection approval. Pentair Equipment Protection must be notified of a claim in writing not later than fourteen (14) days from the date when Buyer has become aware of such occurrence, or where the defect is such that it may cause damage, immediately, such notice containing a description of how the defect manifests itself.
  • Page 15: Limitation Of Liability

    B. All returns to Pentair Equipment Protection must be securely packed, using original cartons if possible. All returns must have the RMA number visible on the outside of the carton. Pentair Equipment Protection is not responsible for material damaged in transit. Any refrigerant-bearing Goods must be shipped upright for return.
  • Page 16 Pentair Equipment Protection 2100 Ho man Way Minneapolis, MN 55303 USA +1.763.422.2211 +1.763.576.3200 PentairEquipmentProtection.com © 2013 Pentair Equipment Protection 88047465 Rev. E P/N 10-1008-239 RSPSupply - 1-888-532-2706 - www.RSPSupply.com http://www.RSPSupply.com/p-19627-Hoffman-T622246G400-T-Series-AC-460V-23500-BTU-Outdoor.aspx...

This manual is also suitable for:

T62

Table of Contents