Function
d07
Valve Protection
d08
Frost Setpoint
Maximum limitation of
d12
heating setpoint
Minimum limitation of
d13
cooling setpoint
d18
Heat/Cool Mode Selection
d19*
Cooling Blocked
Actuators loading selection
d20
for different temperature
compensation.
*Cooling Blocked - at „1" we block cooling for a single room until the device receives a heating command. During the blocking of the cooling function
no message is displayed.
*Please note!
d19 parameter will be available only if d18 is set on 1 (Heat/Cool Mode selection Connected).
22
Parameter
Values
0
Valve protection function is intended to protect thermostatic valves against
getting stuck or jamming (e.g. in summer time when heating system is disa-
bled). If thermostat doesn't send a signal for heating for a period of 7 days, then
1
heating is turned on for a very short period of time just to move the actuators.
In Frost protection mode the thermostat is displaying actual room tem-
perature and maintain „frost protection" setpoint temperature specified
5°C - 7°C
in thermostat settings. When thermostat works in Frost protection
mode then you have no possibilities to change temperature setpoint.
This parameter allows to limit temperature setpoint range by setting
5°C - 35°C
maximum setpoint for heating and cooling modes. Default temperature
This parameter allows to limit temperature setpoint range by setting
5°C - 40°C
minimum setpoint for heating and cooling modes. Default temperature
0
1
0
1
1
2
3
4
5
Description
Enable/Disable.
setting range: 5⁰C - 35⁰C
setting range: 5⁰C - 40⁰C
No connection
Connection
Cooling allowed
Cooling disabled
x1 actuator loading
x2 actuators loading
x3 actuators loading
x4 actuators loading
x5 actuators loading
Default
Values
1
5.0°C
35°C
5°C
0
0
1