Spindle actuator WMS 306
7
Ø36
2,5m
Technical data:
Item Description:
Operating Voltage:
Max. current consumption:
Max. force:
Stroke:
Speed:
Switch-on duration:
Load switch-off:
Protection type acc. to DIN VDE 0470 Part 1
Temperature cond.:
Connection cable:
Housing:
Note
Installation examples:
Wma 200770-0313
©2007, 2013 WindowMaster A/S
Ø18
Ø14
Ø6,2 / Ø8,2
®WindowMaster is a registered trademark used under licence by WindowMaster Group
Description:
Safety spindle drive to actuate vents and rooflights,
for both smoke extraction and comfort ventilation
- housed in a round aluminium tube,
- maintenance free through permanent lubrication,
- outer parts corrosion-free,
- heat resistant silicone connection cable,
- sturdy construction.
The spindle actuator automatically switches off when
it reache its end positions due to the built-in electronic
load switch-off.
Diagram
1000
800
600
400
200
0
WMS 306
24V DC (+30% -20%). Max.20% residual ripple
1A
600N
300, 500, 750mm
8mm/s (full load)
max. 3 min per 10 min. (30%)
integrated electronic load switch-off
IP 54
-5°C to +75°C
Silicone, grey, 2,5m
Aluminium-tube, natural anodised, EV1
We reserve the right to make technical changes
white
brown
Note:
Ensure that the actuator voltage coincides with that
indicated on the type plate.
Only permit fully trained qualified personnel to carry
out installation and maintenance work.
It must be ensured that all pertinent and valid
regulations and guidelines are adhered to.
The user/owner has to check and if necessary adapt
all dimensional information on site.
Check the electrical installation prior to starting up in
accordance with the national safety regulations.
Stroke (mm)
Op Cl
Rated voltage
24V DC
page 1 of 2

Advertisement

loading

Summary of Contents for Window Master WMS 306

  • Page 1 Technical information Spindle actuator WMS 306 Ø18 Description: Ø14 Ø6,2 / Ø8,2 Safety spindle drive to actuate vents and rooflights, for both smoke extraction and comfort ventilation - housed in a round aluminium tube, - maintenance free through permanent lubrication,...
  • Page 2 Technical information Spindle actuator WMS 306 Start-up: Note: For the correct activation of 24V/DC safety actuators Possible danger to persons caused by electric motor (for the technical safety function of the smoke driven sash and frame. extraction) it must be ensured that the smoke and...