Installation Guide | VLT®Safety Option MCB 152
7. Edit the required PROFIsafe settings under the Properties tab.
The following 3 parameters can be changed, but normally it is only necessary to change the F_Dest_Add parameter:
F_Source_Add - the PROFIsafe address of the PROFIsafe master.
F_Dest_Add - the destination address of the safety option. This address must be the same as set in the VLT® Motion Control
Tool MCT 10 software, parameter 42-61 Destination Address.
F_WD_Time - the watchdog time for the PROFIsafe connection. This setting depends on the speed of the PROFINET
connection and the number of slaves.

6.5.2 Programming Safety Functions with Siemens Step 7 and TIA Portal

Refer to the Siemens documentation for more information on distributed safety. Refer to the following documentation for information
on how to use safety inputs and outputs for passivation and reintegration.
Industrial Software SIMATIC Safety - Configuring and Programming. Programming and Operating Manual.
Fail-safe Controllers SIMATIC Safety Integrated. Emergency Stop with Acknowledgment in Category 4 according to EN 954-1.
Fail-safe Controllers SIMATIC Safety Integrated. Passivation and Reintegration of F-I/O considering as example the ET 200S.
Danfoss A/S © 2020.02
Configuring the Safety Option
AN327351953089en-000101 / 130R0578| 47