10. Indoor Unit Function DN Code

<RBC-AMT21E>
4
6
1
5
<Procedure> To be performed only when system at rest
1
Push the
+
+
TEST
SET
CL
seconds.
The unit No. displayed first is the address of the header indoor unit in
group control. Then the fan and louver of the selected indoor unit move.
2
Each time the "Select unit" side of the
the indoor unit Nos. under group control is displayed in turn.
Then the fan and louver of the selected indoor unit move.
3
Use the
button to select the CODE No. (DN code) of the
TEMP.
desired function.
4
Use the
button to select the desired SET DATA associated with
TIME
the selected function.
5
Push the
button. (The display changes from flashing to steady.)
SET
• To change the selected indoor unit, go back to step
• To change the selected function, go back to step
6
When the
button is pushed, the system returns to normal off state.
TEST
TYPE
DN code [10]
Setup data
0000
1-way Air Discharge Cassette
1
0001*
4-way Air Discharge Cassette
0002
2-way Air Discharge Cassette
0003
1-way Air Discharge Cassette (Compact type)
0004
Concealed Duct Standard
0005
Slim Duct
0006
Concealed Duct High Static Pressure
0007
Under Ceiling
0008
High Wall
0010
Floor Standing Cabinet
0011
Floor Standing Concealed
0013
Floor Standing
0014
Compact 4-way Air Discharge Cassette
0016
Fresh Air Intake indoor unit (Duct type)
0018
Console
0050
DX coil
*1 Default value stored EEPROM mounted on service P.C. board.
NOTE: Setup data 0016, 0018, 0050 is RBC-AMT32E only.
<RBC-AMT31E>
3
4
2
FILTER
RESET TEST
3
6
buttons simultaneously and hold for at least 4
UNIT LOUVER
Type
CODE No.
SET
DATA
SETTING
UNIT No.
R.C.
No.
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SWING/FIX
VENT
SET CL
UNIT
1
2
button is pressed, one of
2
.
3
.
Abbreviated Model name
∗∗∗
MMU-AP
SH
∗∗∗
MMU-AP
H
∗∗∗
MMU-AP
WH
∗∗∗
MMU-AP
YH
∗∗∗
MMD-AP
BH
∗∗∗
MMD-AP
SPH, SH
∗∗∗
MMD-AP
H
∗∗∗
MMC-AP
H
∗∗∗
MMK-AP
H
∗∗∗
MML-AP
H
∗∗∗
MML-AP
BH
∗∗∗
MMF-AP
H
∗∗∗
MMU-AP
MH
MMD-APHFE
∗∗∗
MML-AP
NE-H
∗∗∗
MMD-VNK
– 44 –
<RBC-AMT32E>
SET DATA
SETTING
TEMP.
3
TIMER SET
4
TIME
5
FILTER
RESET
TEST
SET
6
1
<RBC-AMT21E button>
1
,
2
3
4
and
5
6
<RBC-AMT31E button>
2
UNIT
Indoor unit capacity
DN code [11]
Setup data
0000*
0001
0003
0005
0007
0009
0011
0012
0013
0015
0017
0018
0021
0023
~
HEXE
CODE No.
UNIT No.
R.C.
No.
ON / OFF
FAN
MODE
SAVE
VENT
5
CL
SWING/FIX
UNIT LOUVER
2
and
and
Model
1
Invalid
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
056 type
072 type
096 type