3. WIreless Remote Contoroller
Type Name
: RBC-AX31U(W)-E
Part No.
: Not assigned
Substitution
: NO
Type of Remote : Wireless remote controller kit
Reference
: NO
Product used
: Light commercial
Note
: *4-way
Type Name
: RBC-AX31U(WS)-E
Part No.
: Not assigned
Substitution
: NO
Type of Remote : Wireless remote controller kit
Reference
: NO
Product used
: Light commercial
Note
: *4-way
*Color of receiver panel is black
*Refer to Hand Unit and Receiver
66.6
(Black type)
Category
DI
OK
SDI
OK
MiNi-SMMS
OK
SMMS
OK
SHRM
OK
SMMS-i
OK
SHRM-i
OK
– 7 –
How to wire the signal receiving
Connection diagram
Indoor unit
Rmote controller
connection
terminal block
Connection
Connect the wires from the signal receiving part to the
remote controller connection terminal block of the indoor
unit. (The terminals are nonpolar.).
• Clamp the redundant portion of the wires with the
clampers in the electric parts box.
Electric parts box
Indoor unit remote
contoroller connection
teriminal block
Clampaers
Controlling one indoor unit by two remote controllers
• Header and follower indoor units are operable even if they
are attached to any indoor unit.
Wireless remote
controller kit * (Header)
(Separately sold)
Signal
receiving part
Remote controller
connection
terminal block
Indoor unit
Earth
2
* Use 0.5 to 2 mm
wires for on-site wiring.
* The total length of wires should be 400m or less.
Performing group control of multiple indoor units by
two remote controllers.
• Header and follower indoor units are operable even if they
are attached to any indoor unit.
Wireless remote
controller kit * (Header)
(Separately sold)
Signal
Remote controller inter-unit
receiving
wiress for group control
part
(Procured on site)
Remote
controller
connection
terminal
block
Earth
Indoor unit No.1
Indoor unit No.2
Earth
2
* Use 0.5 to 2 mm
wires for on-site wiring.
* The total length of inter-unit wires should be 200m or less.
Remote controller test run setup
Perform usual operations using the remote controller to check for
normal operation. A test run can be executed forcibly by using the
following procedure if the room temperature is too high to turn off
the thermostat.
1. Turn off the power of the air conditioner, and remove the screws
to detach the signal receiving part cover.
2. Set bit 1 of DIP switch S003 on the signal receiving part P.C.
board to ON.
3. Attach the signal receiving part to the ceiling panel by reversing
the procedure of removal, and then turn on the power of the air
conditioner.
4. Push [START/STOP] button on the wireless remote controller,
and select COOL or HEAT with [Mode] button.
(Temperature cannot be controlled during a test run.)
5. All LEDs on the signal receiving part flash during a test run.
6. After the test run has been completed, be sure to set bit 1 of DIP
switch S003 to OFF and confirm that the LEDs do not flash.
7. Clamp the wires properly with the clamper secured together with
the signal receiving part cover.
Note1: Use the forced test run only for test run because it overloads
the air conditioner.
Note2: The remote controller is disabled for approx. 1 minute after
power-on, but this is normal. The signal from the remote
controller is received, but the receive data is discarded.
Signal receving part
White
Black
white
Signal
receiving
part
Clamping claw
Wired remote
controller * (Follower)
Remote controller wiress
(procured on site)
Wired remote
controller * (Follower)
(Separately sold)
Earth
Earth
Indoor unit No.3
Indoor unit No.4