9.1.2. Functions
The CDP control panel serves as the basic user interface for operating and
monitoring the drive when the local operating mode has been selected.
The CDP control panel can be attached to or detached from the drive without
having to switch off the auxiliary power supply first.
Using the CDP control panel, it is possible to:
–
Enter startup data
–
Enter reference values
–
Enter start, stop and direction commands
–
Display actual values (three values can be read simultaneously)
–
Display and adjust parameters
–
Display information on the most recent 64 fault events
9.2. Modes
The CDP control panel provides the following modes:
–
"9.2.1 Identification mode" on page 186
–
"9.2.2 Actual signals mode" on page 188
–
"9.2.3 Parameters mode" on page 195
–
"9.2.4 Functions mode" on page 200
–
Drive mode (not used)
9.2.1. Identification mode
The identification mode informs the user about the CDP control panel version and
the ID number of the drive. The information appears on the display
–
when the power supply is switched on, or
–
when the CDP control panel is connected to the drive and the auxiliary voltage
has been switched on already.
When the CDP control panel is initialized, the display changes as follows:
CDP312 PANEL V5.30
...........
After 2-3 seconds the display shows the drive name (1, 2), the application software
in use (3), and the drive identification (4) is displayed.
PRODUCT
ACS6000
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS212794 E01
CDP CONTROL PANEL
REV.
LANG.
PAGE
N
en
186/266