8.8.2. Stop sequence of the drive
1)
Operation
2)
ReadyRef
3)
Stop command
4) Stopping
•
Speed ramps down
•
INU stops modulating
5)
Off command
•
Stop command to ARU (only in drives with an ARU)
•
MCB opens
•
DC link discharges
•
Cooling system switches off after a delay
6) ReadyRun
7)
ARU ReadyOn
•
Only in drives with an ARU
8) ReadyOn
•
Drive is grounded
•
Doors in medium voltage units are released for opening
•
Auxiliary power supply switched off
9) NotReadyOn
PRODUCT