Midea MHC-96HWD1N1(A) Service Manual page 43

R410a full dc inverter split duct 50hz side air-discharge type
Hide thumbs Also See for MHC-96HWD1N1(A):
Table of Contents

Advertisement

MCAC-UTSM-201503
E8: Outdoor unit address is wrong
E8: Outdoor unit address is wrong
The ODU's address is more than 3 or
be set repeatedly
No
Main board is disabled
E9: Eeprom error
H0: Communication error between main control chip and module chip;
H1: Communication error between main control chip and communication chip
Power
supply
transformer 1 and transformer 2
terminals are abnormal
The transformer on main control
board is disabled
There
interference nearby the unit. Such
as High-frequency transmitter or
other high strength radiation device
Outdoor main control board is
damaged
H0/H1
for
main
PCB,
No
No
has
electromagnetic
No
R410A Full DC Inverter Split Duct Type Technical Manual
Yes
Ye
Provide normal power supply
s
Ye
Replace the transformer
s
Ye
Remove the interference
s
Ye
Replace the outdoor main control
s
board
The addresses should be set less
than 3 and differently
No
Replace main board
42