Connection Of Refrigerant Pipe - Midea MHC-96HWD1N1(A) Service Manual

R410a full dc inverter split duct 50hz side air-discharge type
Hide thumbs Also See for MHC-96HWD1N1(A):
Table of Contents

Advertisement

MCAC-UTSM-201503
C and D is connecting pipes interface of indoor and outdoor units
3.6 Heat Insulation
Do the heat insulation to the pipes of air side and liquid side separately. The temperature of the pipes of
air side and liquid side when cooling, for avoiding condensation please do the heat insulation fully.
The air side pipe should use closed cell foamed insulation material, which the fire-retardant is B1
grade and the heat resistance over 120° C.
When the external diameter of copper pipe≤Φ12.7mm, the thickness of the insulating layer at least
more than 15mm;
When the external diameter of copper pipe≥Φ15.9mm, the thickness of the insulating layer at least
more than 20mm.
Please use attached heat-insulating materials do the heat insulation without clearance for the
connecting parts of the indoor unit pipes.

4. Connection of Refrigerant Pipe

4.1 Size of outdoor unit pipes and piping methods
R410A Full DC Inverter Split Duct Type Technical Manual
Check point of indoor unit
A
B
Check point of outdoor unit
D
Indoor unit
C
32