Rheem RIDH09AVFJ Design & Technical Manual page 43

Duct type air conditioner
Hide thumbs Also See for RIDH09AVFJ:
Table of Contents

Advertisement

10) Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
Standard insulation "00" allows system to rapidly respond to the cooling or heating load
changes.
High insulation "01" is when the heat insulation structure of the building is high and does not
require system to rapidly respond to cooling or heating load changes.
When High insulation "01" is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F
(0.0°C)].
Function number
95
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 92, 93).
IF Function 95 is not set first, Room temperature control settings (Function 30, 31, 92, 93) will
be reset and you must re-do them again.
Setting value
Setting description
00
Standard insulation
01
High insulation
- (01 - 40) -
(  . . .Factory setting)