2. DIMENSIONS MODELS :RIWH09AVFJ, RIWH12AVFJ Unit: in (mm) 8-1/16 (204) 34-1/4 (870) [34-1/4 (870)] 16-3/4 (426) 17-1/2 (444) 12-3/16 (310) 11-5/8 (295) Outline of unit 6-1/2 (165) 5-11/16 (144) 2-9/16 (65) 2-9/16 (65) for pipe inlet for pipe inlet...
Page 6
INSTALLATION PLACE Unit: in (mm) Outline of unit 1 (25) or more 3 (52) or more 4 (86) or more 6 (144) or more 60 (1,500) or more - (01-03) -...
5. FAN PERFORMANCE Conditions: Fan speed: HIGH 5-1. AIR VELOCITY DISTRIBUTION Operation mode: FAN MODELS :RIWH09AVFJ, RIWH12AVFJ (ft.) Unit : ft./s (m/s) TOP VIEW Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 3 (1) 2 (0.5) 7 (2) (ft.)
5-2. AIR FLOW MODELS :RIWH09AVFJ, RIWH12AVFJ zCooling Number of Fan speed rotations Air flow (r.p.m.) HIGH 1320 1160 QUIET zHeating Number of Fan speed rotations Air flow (r.p.m.) HIGH 1320 1160 QUIET - (01-09) -...
7. ELECTRICAL CHARACTERISTICS Model name RIWH09AVFJ RIWH12AVFJ Voltage 208 / 230 ~ Power supply Frequency Max. operating current Connection cable Wiring spec. *1 Limited wiring length ft.(m) 68 (21) 1*: Wiring specification Selected sample (Selected based on Japan Electrotechnical Standards and Codes Committee E0005)
9. EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS CNA01 Control input See external CNB01 Operation status output input/output settings for details. CNB02 Error status output 9-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop or Forced stop) The air conditioner can be remotely operated by means of the following on-site work. "Operation/Stop"...
Page 18
zWhen function setting is in "Forced stop" mode Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity zParts (Optional) Parts name Model name External connect kit RXXWZXZ5 Communication kit RXXCBXZ2 * For operating the EXTERNAL function, the wall mounted type requires the communication kit in addition to the wire (RXXWZXZ5).
9-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. zCircuit diagram example Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *33ft. (10m) Signal Optional parts...
Page 20
ERROR STATUS OUTPUT An air conditioner error status signal can be output. zCircuit diagram example Indoor unit control PC board Communication kit Connected unit Connector 24V DC Ex.)Relay unit Ex.)Display Relay power supply *33ft. (10m) Signal Optional parts Locally purchased *: Make the distance from the PC board to the connected unit within 33ft.
11. FUNCTION SETTINGS 11-1. INDOOR UNIT (Setting by remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction. •...
Page 23
FUNCTION DETAILS Functions 1) Filter sign 2) Room temperature control for indoor unit sensor 3) Auto restart 4) Room temperature sensor switching 5) Remote controller custom code 6) External input control 7) Room temperature sensor switching (Aux.) 8) Indoor unit fan control for energy saving for cooling 9) Room temperature control for wired remote controller sensor 10) Heat Insulation condition (building insulation) 1) Filter sign...
Page 24
3) Auto restart Enable or disable automatic restart after a power interruption. ( ... Factory setting) Function number Setting value Setting description Enable Disable * Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
Page 25
8) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. ( ... Factory setting) Function number Setting value Setting description Disable ...
Page 26
REMOTE CONTROLLER CUSTOM CODE SETTING Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the air conditioner has not been set for the matching custom code.) 1.
12. OPTIONAL PARTS 12-1. CONTROLLERS Exterior Parts name Model No. Summary Large and full-dot liquid crystal Monitor Mo 10:00AM screen, wide and large keys Mode Set temp. Wired remote easy to press, user-intuitive ° F Cool High RXRVNUM Icon check: Menu controller arrow key.
Page 28
2. OUTDOOR UNIT SINGLE TYPE : ROSH09AFWJ ROSH12AFWJ DTR_AO230E_01 2017.01.27...
1. SPECIFICATIONS Type INVERTER HEAT PUMP Model name ROSH09AFWJ ROSH12AFWJ Power sourse 208/230V~60HZ Available voltage range 187-253V~60HZ Starting current Cooling 995(1690) 1036(1760) Airflow rate Heating 906(1540) 889(1510) Type×Q'ty Propeller fan×1 Motor output Cooling Sound pressure level dB(A) Heating 19-13/16×25-1/4×1-7/16 19-13/16×35-1/4×1-7/16 Dimensions (H×W×D) 504×642×36.4...
2. DIMENSIONS MODEL : ROSH09AFWJ Unit : in.(mm) 13/16 (20) 26 (660) 2-11/16 (68) 3/8 (10) 11-7/16 (290) 11/16 (18) 13-7/8 (352) 17-7/8 (454) 5-5/16 (135) Unit : in.(mm) INSTALLATION PLACE CAUTION • When the outdoor temperature is 32 °F (0 °C ) or less, do not use the accessory drain pipe and drain cap.
Page 32
MODEL : ROSH12AFWJ Unit : in.(mm) 13/16 (20) 31-1/8 (790) 2-11/16 (68) 3/8 (10) 11-7/16 (290) 11/16 (18) 13-7/8 (352) 21-1/4 (540) 8-1/4 (209) Unit : in.(mm) INSTALLATION PLACE CAUTION • When the outdoor temperature is 32 °F (0 °C ) or less, do not use the accessory drain pipe and drain cap.
7. AIR FLOW MODEL : ROSH09AFWJ zCooling Number of rotations Air flow (r.p.m.) 1690 zHeating Number of rotations Air flow (r.p.m.) 1540 MODEL : ROSH12AFWJ zCooling Number of rotations Air flow (r.p.m.) 1760 1036 zHeating ...
9. ELECTRIC CHARACTERISTICS Model Name ROSH09AFWJ ROSH12AFWJ Voltage 208 / 230~ Power Supply Frequency Starting Current MAX. CKT. BKR *1) Wiring Spec. Power Cable *1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E00005) MCA: Min Circuit Amp(Calculation based on UL1995) MAX.
10. SAFETY DEVICES Model Protection form ROSH09AFWJ ROSH12AFWJ Current fuse 250V 20A (IN THE INVERTER CASE) 250V 5A Circuit protection Current fuse 250V 15A (MAIN PRINTED ─ 250V 3.15A CIRCUIT BOARD) OFF: 212±27°F (100±15°C) OFF: 302±27°F (150±15°C) Fan motor protection Terminal protection program ON: 203±18°F (95±10°C) ON: 230±18°F (120±15°C)