Extension Modules Connectable To Rtu-Ecat - Delta RTU-ECAT Operation Manual

Ethercat remote io communication module
Table of Contents

Advertisement

Environment
Item
Specification
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge, 6KV Contact
Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Noise Immunity
Communication I/O: 2KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3) : 80MHz ~ 1000MHz, 10V/m; 1400MHz
~ 6000MHz, 3V/m
Operation
0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage
-25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
Vibration/shock
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
resistance
68-2-27 (TEST Ea)
Safety
Conforms to IEC 61131-2, UL 61010-1, UL 61010-2-201
Operating: 1080~795hPa (-1000~2000m)
Barometric
pressure-altitude
Storage: 1080~660hPa (-1000~3500m)
Weight
84g
2.3

Extension Modules Connectable to RTU-ECAT

R T U-EC AT
PO WER
RU N
AL AR M
5
x 10
5
R UN
x 10
ST O P
Digital modules connectable to RTU-ECAT
DI/DO module
(Model name)
DVP08SM11N
DVP08SM10N
DVP16SM11N
1
0
Default I/O mapping data
(EtherCAT master → RTU-ECAT)
N/A
N/A
N/A
Chapter 2 Overview
Default I/O mapping data
(RTU-ECAT → EtherCAT master)
8 bits
8 bits
16 bits
2_
2-3

Advertisement

Table of Contents
loading

Table of Contents