Configuration - Salus Optima ST880ZB Manual

Wireless hvac thermostats
Hide thumbs Also See for Optima ST880ZB:
Table of Contents

Advertisement

Section 3

Configuration

Instructions for Thermostat configuration are intended for qualified installation/service
professionals. Do not make adjustments without a thorough understanding of the HVAC system.
Pressing the Settings Icon
setup functions .
-
Press the Settings Icon to move to the next parameter or function
-
Press and hold
-
To change a value, use the + or - Icons
-
To save a value, press
Home Screen . The value will also be saved if the display times out after 10 seconds .
Settings / Functions
Functions
1 - Temperature Units
US Customary or SI Metric
Range: °F – Fahrenheit (US Default)
°C – Celsius (CA Default)
3 - Display Mode
Full Display (Default)
4 - Display On Time
Duration of screen display with no activity
15 Seconds
10 Seconds (Default)
5 Seconds
Range: DM (Display dims to level 1 after 10 seconds
of inactivity)
Module 4 – Wireless HVAC Thermostats
ST898ZB Optima S Thermostat
will begin cycling through all available configuration settings and three
for approximately 1 second to go the previous screen
to move on to the next screen or press any non-icon area to return to the
Shows the network icon,
humidity, button outlines
and time display
(if available)
2 - Display Screen
Brightness Level
Range: 1 to 10
Range: The Optima S has two versions of the home screen
– Full or Simple Display
5 - Set Point Span
Set point dead band between call for heat and shut
down . For example, if Span is set to 1°F and the heating
set point is 70°F, the thermostat calls for heat at 69°F
and shuts off at 70°F
Range: °Fahrenheit - 0 .5°F to 2°F
°Celsius – 0 .25°C to 1°C
Simple Display
The button outlines,
network, time and
humidity displays are
turned off
3-10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Optima s st898zb

Table of Contents