Function Block Assignment Of D.h.w. Heating; Operating Line; Assignment Of D.h.w. Heating - Siemens RVD230 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

80/130
Siemens Building Technologies
HVAC Products
20
Function block Assignment of d.h.w.
heating
20.1

Operating line

Line
Function, parameter
125

Assignment of d.h.w. heating

20.2
Assignment of d.h.w. heating
Operating line 125 is used to select for which controllers in an LPB system the d.h.w. is
heated or, in other words, which heating circuits get their d.h.w. from the same source.
With plant types 1–0 and 5–0, this setting is not required since they do not include
d.h.w. heating.
Operating line 125 Explanation
0
The d.h.w. is only provided for the heating circuit associated with
the own controller.
1
The d.h.w. is only provided for the heating circuits of the control-
lers with the same segment number that are connected to the
data bus (LPB).
2
The d.h.w. is provided for all heating circuits of the controllers
connected to the data bus (LPB).
The setting is active only when setting 1 (according to the space heating switching
program with forward shift) has been selected on operating line 101 (d.h.w. release).
Basic Documentation RVD230

20 Function block Assignment of d.h.w. heating

Unit
Factory setting
0
Range
0...2
CE1P2383en
27.05.2004