Siemens Building Technologies
HVAC Products
1
Summary
1.1
Brief description and key features
• The RVD230 is a multifunctional heating controller for controlling the flow temperature
of the heating circuit and of d.h.w. heating
• The controller's field of use covers exclusively plants with district heat connections. It
has been specially designed for small to medium-size residential and nonresidential
buildings
• The RVD230 has 7 heating circuit types and 11 d.h.w. plant types preprogrammed. By
combining the different plants, it is possible to configure 28 plant types. The configura-
tion activates all functions and settings required for the respective type of plant
• In terms of control, the RVD230 is designed as a flow temperature controller. Control
can be effected in 1 of 5 different ways:
Weather-compensated control of the heating circuit flow
−
Weather- and room temperature-compensated control of the heating circuit flow
−
Room temperature-compensated control of the heating circuit flow
−
Demand-dependent control of the common flow
−
Demand-compensated precontrol
−
• In terms of d.h.w. heating, the RVD230 is designed for the following types of applica-
tions:
D.h.w. heating with coil type storage tanks
−
D.h.w. heating with stratification storage tanks
−
Direct d.h.w. heating via heat exchanger
−
Common or separate heat exchangers for the heating circuit and d.h.w. heating
−
2-stage separation of the d.h.w. from district heating
−
• The RVD230 is suited for the control of 2-port and 3-port valves as well as diverting
valves and pumps, including variable speed pumps
• For the direct adjustment of the nominal room temperature setpoint, a setting knob is
available. All the other parameters are set digitally based on the operating line principle
• Key design features: Operating voltage AC 230 V, CE conformity, overall dimensions
to DIN 43700 (96 × 144 mm)
1.2
Type summary
The RVD230 is a compact controller and requires no accessories such as inserts, plug-
in modules, etc. The controller is supplied complete with base.
1.3
Equipment combinations
1.3.1
Suitable sensors
• For the flow temperatures:
Suitable are all types of temperature sensors that use a sensing element LG-Ni 1000.
The following types are presently available:
Strap-on temperature sensor QAD22
−
Immersion temperature sensors QAE2...
−
• For the control of the d.h.w. flow temperature (B3), it is also possible to use commer-
cially available sensors with Pt 500 sensing elements
• For the return temperatures:
The following types of temperature sensors are presently available:
Strap-on temperature sensor QAD22
−
Immersion temperature sensors QAE2...
−
Basic Documentation RVD230
1 Summary
13/130
CE1P2383en