Technical Data - Siemens RVD230 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

Power supply
Functional data
Classifications to
EN 60730
Inputs
Sensor inputs (B...)
Digital input (H5)
Outputs
Switching outputs
PMW output
Interfaces
PPS
LPB
Perm. cable lengths
Degrees of protection
Siemens Building Technologies
HVAC Products
35

Technical data

Rated voltage
Rated frequency
Max. power consumption
Reserve of clock
Software class
Mode of operation
Degree of contamination
Sensing element
Max. number of sensors per input
Measuring range
Low-voltage up to
Switching current
Voltage with contact open
Voltage with contact closed
Contact resistance
Rated switching voltage
Rated current
Outputs Y1, Y2, Q1, Q2, Q3, Y7/Q4, Y8/K6 AC 0.02...1(1) A
Outputs Y5, Y6
Switch-on current
Max. rating as mixing valve relay Y1, Y2, Y5,
Y6, Y7, Y8
Idle voltage
Max. internal resistance
Frequency
Connection (to the room unit)
Connection
Bus loading number E
Detailed information for Standard Controls:
Basic System Data
Local Process Bus
Detailed information for OEMs:
Local Process Bus
To the sensors
Copper cable 0.6 mm dia.
Copper cable 1.0 mm
Copper cable 1.5 mm
To the room unit
Copper cable 0.6 mm dia.
Copper cable ≥0.8 mm dia.
Degree of protection of housing to IEC 60529 IP 40D
Safety class to EN 60730
Basic Documentation RVD230
35 Technical data
AC 230 V ±10 %
50 Hz
8.5 VA, 6.5 W, cos ϕ >0.7
12 h
A
type 1b (automatic controls)
normal contamination
refer to subsection 1.3 "Equipment
combinations"
1
0...150 °C
U <10 V
I ≥2 mA (for reliable operation)
DC 12 V
DC 2...5 mA
R ≤80 Ω
AC 24...230 V
AC 0.02...2(2) A
max. 10 A max. 1 s
15 VA
12 V
1,340 Ω
2,400 Hz
2-wire connection, interchangeable
2-wire connection, not interchangeable
3
Data Sheet N2030
Data Sheet N2032
Basic Documentation P2370
20 m
2
80 m
2
120 m
37 m
75 m
II
117/130
CE1P2383en
27.05.2004

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents