Frost Protection For D.h.w; Switching D.h.w. Heating Off - Siemens RVD230 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

66/130
Siemens Building Technologies
HVAC Products
16.8

Frost protection for d.h.w.

The d.h.w. circuit is protected against frost. Frost protection for the d.h.w. is activated
when the d.h.w. temperature drops below 5 °C, independent of the operating mode.
The charging pump (plant types 2–11 and 2–12: the diverting valve) will be activated
and a d.h.w. temperature of at least 5 °C will be maintained.
Frost protection is ensured
• when d.h.w. heating is ON (operating mode button
• when d.h.w. heating is OFF (operating mode button
• when, in the local heating circuit, the holiday function is active (operating mode button
flashes)
• when, with the RVD230 as a primary controller, the holiday function is active in the
heating circuits of the zone controllers assigned via LPB (operating mode button
lit)
With all plant types no. x–4, frost protection for the d.h.w. is not possible.
16.9

Switching d.h.w. heating off

The d.h.w. functions can be deactivated by pressing button "D.h.w. heating ON / OFF"
(LED in the button not lit). Frost protection for the d.h.w. remains active; the d.h.w.
pump(s) will be deactivated.
Manual d.h.w. charging will be terminated, however.
Basic Documentation RVD230
16 Function block D.h.w. heating
lit)
dark)
CE1P2383en
27.05.2004