ACM 150
Figure 28. Relay output wiring
81 Power Fail
82 Watchdog Timer
83 Manual Mode
84 General Malfunction
85 General Alarm 1
86 General Alarm 2
WARNING!
This sequence can cycle repeatedly and may result in an exposure to toxic gas
while ERT personnel are repairing the leak.
If the ACM 150 monitor output relays are used to shutdown the gas source and
interrupt the gas flow, a latching relay must be used in the control loop. If not,
the ACM 150 monitor relay will shutdown the gas source and stop the leak that
was detected by the ACM 150 monitor. The alarm will soon clear and reset the
relay, restarting the flow of gas, and the leak will be detected again.
ATTENTION!
Cette séquence peut à plusieurs reprises le cycle et peut entraîner une exposition à
des gaz toxiques tandis que le personnel de l'EIU sont la réparation de la fuite.
Si les ACM 150 relais de sortie du moniteur sont utilisées pour arrêter la source de gaz
et interrompre l'écoulement de gaz , un relais de verrouillage doit être utilisé dans la
boucle de commande . Si non, l' ACM 150 moniteur relais arrêt de la source et de gaz
arrêter la fuite que a été détecté par le moniteur ACM 150 . L'alarme sera bientôt claire
et réinitialiser le relais , le redémarrage de l'écoulement du gaz , et la fuite sera à
nouveau détecté .
 
56