3.2.35 DINU_- Digital Inputs, Universal

DINU_ blocks have multi-function capability:
sensing a discrete input and providing a high (1) or low
(0) output representing the state of the input
totalizing and scaling the count of input pulses
converting the rate of input pulses to a scaled analog
frequency output
Two DINU_ blocks are available on the I/O expander board.
The fixed names (IDs) of these blocks and their terminal
designations are listed in Section 8.4.
Output CT represents the scaled (actual count x K) total of
input pulses that occurred since the last reset. This output is a
real number and can be used in a number of applications,
such as a direct count input to the BAT batch totalizer
function block or in math operations, such as computing the
difference between counts in a ratio trim circuit.
Output IS is the current state of the input at the time the
block is executed at the start of each controller scan cycle. It
will be low (0) when the input is low and high (1) when the
input is high.
Output SF is a scaled frequency (using the FREQ MIN and MAX parameters) that can represent flow rate, speed, or
other transmitter variable that has a frequency signal. When the FREQ MAX parameter is set to 25 or less, a 20
msec contact debounce is used. When contact debounce is used, a pulse input must remain on for 20 msec to be
recognized as a valid pulse. Output SF is linear with frequency and can be characterized using the CHR function
block if necessary. An engineering range and units are assigned to this signal using the MINSCALE, MAXSCALE,
DPP, and ENGUNITS parameters. They are available to other blocks using the OR output connection.
Input R resets output CT to 0.0. Input D controls the direction of the count. When direction input D is low (0), the
count will move backwards, including negative values. The direction input feature enables the use of count down
counters and it allows duplication of functions performed by previous computer pulse interfaces having a
Pulse/Direction format. Input TC asserted high (1) will force the scaled count to track an external signal. This can
be used in applications where the CT output is being used to set a value (e.g. setpoint) that can be changed from
another source.
The quality status output QS indicates the
quality of the block outputs and is high (1)
when outputs CT, IS, or SF are of bad
quality. Bad quality indicates a failure in the
hardware conversion circuit.
POWER UP - With PU LAST set to YES, the
CT output will power up at the last value
during a hot or warm start. If set to NO,
during a warm or a cold start, it will be set to
0.0. The digital filter will be temporarily by-
passed during a hot, a warm or a cold start.
March 2003
DIGITAL INPUT - UNIVERSAL
Reset
Direction
Track Variable
Track Command
DINU_+
DINU_-
Z D O
R
E
Q
F
M
I
F R
E
Q
M
A X
K
S
C
A
L
D I G
F I L T
A
L
M
I
N
S
C
M
A X
S
C
A
L
D P P
E
N
G
U N I T S
P U
L A S T
I N P U T
I
N
P
U
T
I
N
P
U
T
T
I N P U T
T
Reset
R
Direction
D
Track Variable
TV
Track Command
TC
DIU_+
Current Limit < 7 mA
.
P/A Converter
DIU_-
BLOCK DIAGRAM
Function Blocks
DINU_
OR
Output Range
R
D
DIGITAL INPUT
CT
Count Total
UNIVERSAL
TV
SF
Scaled Freq.
TC
Input State
IS
QS
Quality Status
Zero Drop Out (Engineering Units)
.. Real
(H)
N
FREQuency MINimum Hz
................ Real
(H)
FREQuency MAXimum Hz
............... Real
(H)
E
K factor SCALE
................................ Real
(H)
DIGital FILTer
....................... 0 to 180 sec
(S)
E
MINimum SCALE
............................. Real
(H)
E
MAXimum SCALE
............................ Real
(H)
D
P
P
ecimal
oint
osition (preferred)
(S)
............. 0.0.0.0.0.0
ENGineering UNITS
............ 6 Char ASCII (PRCT)
(S)
Power Up LAST
.......................... NO/YES
(S)
R
INPUT R
..................
(H)
loop tag.block tag.output
D
INPUT D
..................
loop tag.block tag.output
(H)
V
INPUT TV
................
loop tag.block tag.output
(H)
C
INPUT TC
................
(H)
loop tag.block tag.output
Count
K
Count Total
ENG UNITS
Scaled Freq.
Digital
Scaling
Filter
Quality Test
(0)
(0)
(1000)
(1.0)
(0 sec)
(0.0)
(100.0)
(0.00)
(YES)
(null)
(null)
(null)
(null)
CT
.
SF
IS
QS
3-43